ID
Object_Name
Present_Value
Default
name
Writeable
EEPROM
Parameter Unit
Writeable
Cmd.able
Timeout
Option
AV:37
Reserved for P, I, D
AV:38
AV:39
AV:40
Setpoint 3
2023
%
x
AV:41
Bus
Feedback 3
896
%
x
AV:42
Reserved for P, I, D
AV:43
AV:44
AV:45
Running
Bypass
3111
Hours
MCO 104
AV:46
AV:47
AV:48
AV:49
AV:50
Alarm Log:
Error Code
1530
NONE
AV:51
Fault Code
Note 4
NONE
AV:52
PID Start
Speed
2083
Hz
x
AV:53
On
Reference
Bandwidth
2084
%
x
AV:54
PID Propor-
tional Gain
2093
NONE
x
AV:55
PID Integral
Time
2094
Sec
x
AV:56
PID Differen-
tiation Time
2095
Sec
x
AV:57
PID Diff. Gain
Limit
2096
NONE
x
Table 5.3 Analog Values
1
Either AV:1 or AV:2 controls the drive reference. Only one of them can control the frequency converter at a time and BV:2
decides which one.
2
This value is not directly available in the frequency converter. The value must be calculated as follows:
AV # 3 = Par. 16 − 17
Par. 4 − 13 × 100 %
3
This value is not directly available in the frequency converter. The value must be calculated as follows:
AV # 4 = Par. 16 − 52
Par. 20 − 14 × 100 %
4
VLT
®
HVAC Drive fault codes are transmitted as an analog value in AV:51. The Fault codes are mapped as shown in table on
following page. The VLT
®
HVAC Drive alarm codes are shown as well for comparison.
BACnet Objects
VLT
®
HVAC Drive Native BACnet Operating Instructions
MG.14.C1.02 - VLT
®