5.3.1 Object/Property Support Matrix
The following table summarises the Object Types and Properties supported:
Property
Device
Binary
input
Binary
output
Binary
value
Analog
input
Analog
output
Analog
value
Multistage
value
Object identifier
X
X
X
X
X
X
X
X
Object Name
X
X
X
X
X
X
X
X
Object Type
X
X
X
X
X
X
X
X
System Status
X
Vendor Name
X
Vendor Identifier
X
Model Name
X
Firmware Revision
X
Appl. Software Revision
X
Location
X
Description
X
Protocol Version
X
Protocol Revision
X
Services Supported
X
Object List
X
Max. APDU Length
X
Segmentation Support
X
Local Time
X
Local Date
X
APDU Timeout
X
Number APDU Retries
X
Max Master
X
Max Info Frames
X
Device Address Binding
X
Database Revision
X
Present Value
X
X
X
X
X
X
X
Status Flags
X
X
X
X
X
X
X
Event State
X
X
X
X
X
X
X
Reliability
X
X
X
X
X
X
X
Out-of-Service
X
X
X
X
X
X
X
Number of States
X
State Text
X
Units
X
X
X
Priority Array
X
X*
X
X*
X*
Relinquish Default
X
X*
X
X*
X*
Polarity
X
X
Active Text
X
X
X
Inactive Text
X
X
X
*For commandable values only
BACnet Objects
VLT
®
HVAC Drive Native BACnet Operating Instructions
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark
21
5
5