ID
Object_Name
Present_Value
Default
name
Writeable EEPROM
Parameter
Bit
number
Writeable Cmd.able EEPROM
Timeout
Option
BV:0
Reserved for VFD profile
BV:1
RUN/STOP
Command x
x
CTW=047c
+
Reversing
6 reverse
15
x
x
x
bit 15
BV:2
REF 1 / REF
2 Select
x
x
Note 1
n/a
x
x
x
x
BV:3
Fault Reset
Command x
x
CTW
7
x
BV:4
RUN / STOP
Monitor
x
x
STW
1
BV:5
OK / FAULT
Monitor
x
x
STW
3, 6, 7
BV:6
HAND /
AUTO
Reference
x
x
16-95
1
BV:7
Reserved for VFD profile
BV:8
BV:9
BV:10
BV:11
BV:12
BV:13
BV:14
BV:15
BV:16
BV:17
BV:18
BV:19
BV:20
BV:21
Warning
x
x
STW
7
BV:22
Trip
x
x
STW
3
BV:23
Triplock
STW
6
BV:24
Coasting
CTW
3
x
x
x
BV:25
CW/CCW
CTW
15
x
x
x
BV:26
Jog
CTW
8
x
x
x
BV:27
Reset
CTW
7
x
x
x
BV:28
Reset KWh
Counter
1506
n/a
x
BV:29
Reset
Running
Hours
Counter
1507
n/a
x
BV:30
Reverse
STW
1
BV:31
Speed =
reference
STW
8
BV:32
Bus control
STW
9
BV:33
Running
x
x
STW
11
BV:34
Ramp 1/
Ramp 2
CTW
9
x
x
BV:35
ECB Test
Mode
3110
0
MCO 104
BACnet Objects
VLT
®
HVAC Drive Native BACnet Operating Instructions
18
MG.14.C1.02 - VLT
®