8-06 Reset Control Timeout
Option:
Function:
[1]
Do reset Returns the frequency converter to the original
set-up following a control word time-out. When
the value is set to
Do reset
[1], the frequency
converter performs the reset and then
immediately reverts to the
Do not reset
[0] setting.
8-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for
BACnet.
[0]
*
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
8-09 Communication Charset
Option:
Function:
[0]
*
ISO 8859-1
[1]
ANSI X3.4
8-30 Protocol
Option:
Function:
[5] BACnet Communication according to the BACnet protocol as
described in FC 100 Native BACnet Operating
Instructions.
8-31 Address
Range:
Function:
1.
*
[1. - 127. ] Sets the drives MAC ID on the MS/TP network.
8-32 Baud Rate
Option:
Function:
Baud rate selection depends on Protocol
selection in
8-30 Protocol
.
[2]
9600 Baud
[3]
19200 Baud
[4]
*
38400 Baud
[6]
76800 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol
8-30 Protocol
using the FC Port. For
some of the protocols, not all options
will be visible. Default depends on
the protocol selected.
[0]
*
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Function:
Size related
*
[5. - 10000.
ms]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used
for overcoming modem turnaround
delays.
8-36 Maximum Response Delay
Range:
Function:
Size related
*
[11. - 10001.
ms]
Specify the maximum permissible
delay time between transmitting a
request and receiving a response.
Exceeding this delay time will cause
control word time-out.
8-37 Maximum Inter-Char Delay
Range:
Function:
Size related
*
[0.00 - 35.00
ms]
Specify the maximum permissible
time interval between receipt of two
bytes. This parameter activates time-
out if transmission is interrupted.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND
Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Parameters
VLT
®
HVAC Drive Native BACnet Operating Instructions
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark
25