User Guide
|
MCX-RTU Rooftop
RS8KE102 | 19
© Danfoss | ADAP-KOOL® | 2018.11
COL
Parameters >
Cool
Function
Default
Units
Ct1
CL1 Target
Cool 1 Target Temperature (10.0-40.0°C)
40.0
°C/°F
Cb1
CL1 PreDelay
Cool 1 Pre Delay (0-240)
0
m
Ca1
CL1 PostDelay
Cool 1 Post Delay (0-240)
0
m
Ct2
CL2 Target
Cool 2 Target Temperature (10.0-40.0°C)
40.0
°C/°F
Cb2
CL2 PreDelay
Cool 2 Pre Delay (0-240)
240
m
Ca2
CL2 PostDelay
Cool 2 Post Delay (0-240)
240
m
Ct3
CL3 Target
Cool 3 Target Temperature (10.0-40.0°C)
40.0
°C/°F
Cb3
CL3 PreDelay
Cool 3 Pre Delay (0-240)
240
m
Ca3
CL3 PostDelay
Cool 3 Post Delay (0-240)
240
m
Ct4
CL4 Target
Cool 4 Target Temperature (10.0-40.0°C)
40.0
°C/°F
Cb4
CL4 PreDelay
Cool 4 Pre Delay (0-240)
240
m
Ca4
CL4 PostDelay
Cool 4 Post Delay (0-240)
240
m
CLr
CL Range +/-
Cool Range +/- (0.0-10.0K)
0.5
K/F
CL1
CL Ambient
Lockout
Cool Mode Ambient Lockout (0.0-85.0°C)
15.6
°C/°F
CL2
CL Lockout
Range +/-
Cool Mode Ambient Lockout Range +/-
(0.0-10.0K)
1.1
K/F
CnS
CL Night Setback Cool Mode Night Setback (0.0-30.0K)
0.6
K/F
Cs1
CL SupplyAir
Cool Mode Supply Air Target for VS Fan
(0.0-100.0°C)
15.0
°C/°F
Cm1
CL Min Fan
Speed
Cool Mode Min Fan Speed (0.0-100.0)
50.0
%
Cm2
CL Max Fan
Speed
Cool Mode Max Fan Speed (0.0-100.0)
75.0
%
CC1
CL Min Compr 1
Speed
Cool Min Compressor 1 Speed (0.0-100.0)
5.0
%
CC2
CL Min Compr 2
Speed
Cool Min Compressor 2 Speed (0.0-100.0)
30.0
%
CC3
CL Min Compr 3
Speed
Cool Min Compressor 3 speed (0.0-100.0)
30.0
%
CC4
CL Min Compr 4
Speed
Cool Min Compressor 4 speed (0.0-100.0)
30.0
%
CLi
PI Integ Time
120
CLg
PI Gain
8.0
Cns
CL Neutral SA
20.0
°C/°F
Rt1
HR1 Target
Heat Reclaim 1 Target Temperature (10.0-
40.0°C)
22.2
°C/°F