Parameters >
General
Function
Default
Units
y21
Avg RH1
Select RH1 sensor for Average(None/Local/
Glbl1-5)
None
y22
Avg RH2
Select RH2 sensor for Average(None/Local/
Glbl1-5)
None
y23
Avg RH3
Select RH3 sensor for Average(None/Local/
Glbl1-5)
None
y24
Not Used
Not Used
y25
Not Used
Not Used
y30
SelectExhaustFan
Select Exhaust Fan Schedule(0-16)
0
y31
Aux RO 1 Schedule
Select Aux RO 1 Schedule(0-16)
0
y32
Aux RO 2 Schedule
Select Aux RO 2 Schedule(0-16)
0
y33
Aux RO 3 Schedule
Select Aux RO3 Schedule(0-16)
0
y34
Aux RO 4 Sche-
dule
Select Aux RO4 Schedule(0-16)
0
y35
Enable Broadcast Enable Broadcast feature(No/Yes)
Yes
y36
Night Shutdown
Night Shutdown(No/Yes)
No
y37
Enable Logging
Enable Logging(No/Yes)
No
y38
Logging Interval
Set Logging Interval
1
m
FAN
Parameters >
Fan
Function
Default
Units
FN1
Fan Off Delay
Fan Off Delay (0-30)
2
m
FN2
Fan Proof Value
Fan Proof Value (0.0-100.0)
Used with the Fan CT AI . If AI is above this
value the is ON
2.0
a
FN3
Min Fan Speed
Min Fan Speed when in Fan Only Mode
(0.0-100.0)
30.0
%
FN4
Fan PI Gain
Fan PI Gain Value (0.0-100.0)
5.0
FN5
FanPIIntegrati-
onTime
Fan PI Integration Time (6-1000)
60
FN6
Building Press
Target
Building Pressure Target(-1.00-1.00)
0.00
FN7
OvrdFanSpeed
Stage One Fan Speed if exhaust fan one
enabled
FN8
OvrdFanHigh
Stage Two Fan Speed if exhaust fan two
enabled
FN9
Cond Target 1
Condenser Target
350 PSI
bar/psi
FNA
Cond Target 2
Condenser Target if Reheat enabled
400 PSI
bar/psi