ALM Parameters >
Alarm Config
Function
Default
Units
S03
Zone - Low Temp Zone Temp Low Alarm (0.0-40.0)
5.0
°C/°F
S04
Zone - Delay
Zone Temp Delay (0-240)
240
m
S05
CO2 - High Level
CO2 High Alarm (0-2000)
1000
ppm
S06
CO2 - Delay
CO2 Alarm Delay (0-240)
15
m
S07
Fan High Run-
time
Fan High Daily Runtime (0-1500)
1500
m
S08
Fan High Cycle
Fan High Daily Cycles (0-1000)
1000
S09
Cool1 High
Runtime
Cool 1 High Daily Runtime (0-1500)
1500
m
S10
Cool1 High Cycle Cool 1 High Daily Cycles (0-1000)
1000
S11
Cool2 High
Runtime
Cool 2 High Daily Runtime (0-1500)
1500
S12
Cool2 High Cycle Cool 2 High Daily Cycles (0-1000)
1000
S13
Cool3 High
Runtime
Cool 3 High Daily Runtime (0-1500)
1500
m
S14
Cool3 High Cycle Cool 3 High Daily Cycles (0-1000)
1000
S15
Cool4 High
Runtime
Cool 4 High Daily Runtime (0-1500)
1500
m
S16
Cool4 High Cycle Cool 4 High Daily Cycles (0-1000)
1000
S17
Heat1 High
Runtime
Heat 1 High Daily Runtime (0-1500)
1500
m
S18
Heat1 High Cycle Heat 1 High Daily Cycles (0-1000)
1000
S19
Heat2 High
Runtime
Heat 2 High Daily Runtime (0-1500)
1500
m
S20
Heat2 High Cycle Heat 2 High Daily Cycles (0-1000)
1000
S21
Heat3 High
Runtime
Heat 3 High Daily Runtime (0-1500)
1500
m
S22
Heat3 High Cycle Heat 3 High Daily Cycles (0-1000)
1000
S23
Heat4 High
Runtime
Heat 4 High Daily Runtime (0-1500)
1500
m
S24
Heat4 High Cycle Heat 4 High Daily Cycles (0-1000)
1000