User Guide
|
MCX-RTU Rooftop
RS8KE102 | 24
© Danfoss | ADAP-KOOL® | 2018.11
OV0
Service > Over-
rides
Function
Default
Units
OV1
Override Night-
Setback
Override Night Setback – Enables Night
Setback(Off/On)
Off
OV2
Override Title24
Override Title24 – Enables Title24(Off/On)
Off
OV3
Override Fan
Override Fan(Auto/Override)
Auto
OV4
Override Fan %
Sets Speed of Fan when in Override(0.0 –
100.0)
0.0
%
OV5
Override Dam-
per
Override DamperAuto/
Off/25%/50%/75%/100%)
Auto
OV6
Override Cooling Override Cooling(Auto/Off/Stg1/Stg2/
Stg3/Stg4/All On)
Auto
OV7
Override Heat
Reclaim
Override Heat Reclaim(Auto/Off/Stg1/
Stg2/Stg3/Stg4/All On)
Auto
OV8
Override Aux
Heat
Override Aux Heat(Auto/Off/Stg1/Stg2/
Stg3/Stg4/All On)
Auto
OV9
Override Time-
out
Override Timeout – Removes override after
so much time (0-30)
0
m
Overrides OV1 and OV2, are used to enable Night Setback and Title24 modes.
Overrides OV3 – OV8 are used to place the specific features (as shown below) in manual opera-
tion. The override value will be displayed by stage, %, OFF, ON, etc. For analog outputs a value of
zero shuts down the feature and 100 will enable 100% of the feature overridden.
Overrides