2 Introduction
2.1.1 Introduction to the MCO 101 and MCO 102
The MCO 101 and 102 are add-on options which extend the supported number of pumps and the functionalities of the built-in cascade controller in the
VLT
®
AQUA Drive.
The extended cascade controller can be used in two different modes.
It can either be used with the extended features controlled by parameter group 27** or it can be used to extend the number of available relays for the
basic cascade controlled by parameter group 25**.
When one of the cascade options is installed, only group 27 will appear. If the option needs to extend the relays in the built-in cascade controller group
25, the basic cascade can be enabled in parameter 27-10, after which group 25 will be visible again in the main menu. If 27-10 is set to Basic Cascade,
only the basic cascade functionality will be available, but three relays will be added to make a total of five relays.
When using group 27** Extended / Advanced Cascade Control, the systems with pump alternation can be set up with two relays per pump, which reduces
the need for external equipment.
With the MCO 101, a total of five relays can be used in cascade with the MCO 102. A total of eight pumps can be controlled.
NOTE!
If the MCO 102 is installed, the relay option MCB 105 can extend the number of relays to 13.
2.1.2 Extended Cascade Controller, MCO 101, and Advanced Cascade Controller, MCO 102
Cascade control is a common control system used to control parallel pumps or fans in an energy-efficient way.
The Cascade Controller option provides the capability to control multiple pumps configured in parallel in a way that makes them appear as a single larger
pump.
When using cascade controllers, the individual pumps are automatically turned on (staged) and turned off (de-staged) as needed in order to satisfy the
required system output for flow or pressure. The speed of the pumps connected to VLT AQUA Drives is also controlled to provide a continuous range of
system output.
Extended and Advanced Cascade Controller
Option
2 Introduction
MI.38.C2.22 - VLT
®
is a registered Danfoss trademark
2-1
2