Electrical wiring
Figure 8.2: Electrical wiring. Terminal 27 on the master drive is used as pulse output reference. Terminal 29 on the follower drives is used
as pulse input reference. All follower drives are connected to line power and the motor in the same way as the master drive symbolized with
the text:
Line power
and
Motor
.
NOTE!
In the example, it is assumed that the pressure transmitter used as a feedback sensor has a range from 0–10 bar.
Parameter settings:
Display settings - Master drive:
Display Line 1.1 Small
0-20
Reference [1601]
Display Line 1.2 Small
0-21
Feedback [1652]
Display Line 1.3 Small
0-22
Motor current [1614]
Display Line 2 Large
0-23
Frequency [1613]
Display Line 3 Large
0-24
Cascade reference [2791]
Display settings - Follower drives:
Display Line 1.1 Small
0-20
External Reference [1650]
Display Line 3 Large
0-24
Frequency [1613]
NOTE!
Please note: the format of the analog input is set using switch S201 below the LCP.
8 Annex A - Master/Follower Application Note
Extended and Advanced Cascade Controller
Option
8-2
MI.38.C2.22 - VLT
®
is a registered Danfoss trademark
8