[3]
Offline-Off
Turns the pump off and makes the pump unavailable for cascading.
[4]
Offline-On
Turns the pump on and makes the pump unavailable for cascading.
[5]
Offline-Spin
Initiates a pump spin.
27-03 Current Runtime Hours
Option:
Function:
Units: hrs
Current Runtime Hours is a readout parameter showing the total number of hours each pump has
been running since the last reset. This time is used to balance the running hours between pumps.
The times may all be reset to 0 by using parameter 27-91.
27-04 Pump Total Lifetime Hours
Range:
Function:
0*
[0 - 2147483647]
Pump Total Lifetime Hours is the total operating hours for each connected pump. This parameter
may be individually set to any value for maintenance purposes.
6.1.3 Configuration, 27-1*
This parameter group is for configuring the cascade controller option.
27-10 Cascade Controller
Option:
Function:
Cascade Controller Mode sets the operating mode. Possible selections are:
Disabled
Turns off cascade controller option.
Master/Follower
Operates using only variable speed pumps connected to drives. This selection simplifies the set-up.
Mixed Pumps
Operates using both variable and fixed-speed pumps.
Basic Cascade Ctrl
Turns off the cascade option and reverts to basic cascade operation (See parameter group 25-**
in the
VLT AQUA Drive Programming Guide
for further information). The additional relays on the
option can be used to extend the basic cascade with 3 relays. Only basic cascade functions are
available.
27-11 Number of Drives
Range:
Function:
1*
[1 - 8]
Number of adjustable frequency drives to be controlled by the cascade controller.
MCO 101: 1-6
MCO 102: 1-8
27-12 No. of Pumps
Range:
Function:
0*
[0 - No. of Drives]
Number of pumps to be controlled by the cascade controller.
MCO 101: 0-6
MCO 102: 0-8
27-14 Pump Capacity
Range:
Function:
100%*
[0% (Off) - 800%]
Pump Capacity sets the capacity of each pump in the system, relative to the first pump. This is an
indexed parameter with one entry per pump. The capacity of the first pump is always considered
to be 100%.
6 How to Program
Extended and Advanced Cascade Controller
Option
6-2
MI.38.C2.22 - VLT
®
is a registered Danfoss trademark
6