6 How to Program
6.1 Extended Cascade Controller Parameters
Please note that this parameter cannot be adjusted while the motor is
running.
6.1.1 Cascade CTL Option 27-**
Cascade Control Option parameter group.
6.1.2 Control & Status, 27-0*
Control and status parameters are for monitoring and manual control of the pumps.
Use the right [
►
] and left [
◄
] arrow keys to choose a pump. Use the up
[
▲
] and down [
▼
] arrow keys to change settings.
27-01 Pump Status
Option:
Function:
Pump Status is a readout parameter showing the status of each pump in the system. Possible set-
tings are:
[0]
Ready
The pump is available for use by the cascade controller.
[1]
On Drive
The pump is controlled by the cascade controller, and the pump is connected to a drive and running.
[2]
Running on Line Power
The pump is controlled by the cascade controller, and is connected to line power and running.
[3]
Offline-Off
The pump is not available for use by the cascade controller and is off.
[4]
Offline-On Line Power
The pump is not available for use by the cascade controller, and is connected to line power and
running
[5]
Offline-On Drive
The pump is not available for use by the cascade controller, and is connected to line power and
running
[6]
Offline-Fault
The pump is not available for use by the cascade controller, and is connected to line power and
running
[7]
Offline-Hand
The pump is not available for use by the cascade controller, and is connected to line power and
running
[8]
Offline-External Interlock
The pump has been externally interlocked and is off.
[9]
Spinning
The cascade control is executing a spin cycle for the pump.
[10]
No Relay Connection
The pump is not directly connected to a drive, and no relay has been assigned to the pump
27-02 Manual Pump Control
Option:
Function:
Manual Pump Control is a command parameter that allows for the manual control of individual pump
states. Selecting one of these will execute the command and then return to No Operation. Possible
selections are:
[0] *
No Operation
Does nothing.
[1]
Online
Makes the pump available to the cascade controller.
[2]
Alternate On
Forces the selected pump to become the lead pump.
Extended and Advanced Cascade Controller