Variable Speed
Fixed Speed
100%
200%
(no control between 100% and 200%)
100%
100% + 300%
(no control between 200% and 300%)
100%
100% + 200% + 600%
(no control between 400% and 600%)
3.1.7 Mixed Pump Configuration with Alternation
In this configuration, it is possible to alternate the drive between two pumps along with controlling additional fixed-speed pumps. The cascade controller
will attempt to balance the running hours between all of the pumps as specified by the Runtime Balancing parameter.
Figure 3.7: Example 1
The two pumps can be ether variable speed or fixed-speed with equal running hours.
For this configuration, relay selections in Group 27-7* “Connections” are as follows:
27-70 RELAY 1
→
[8] Pump 1 to Drive 1
27-71 RELAY 2
→
[16] Pump 2 to Drive 1
27-72 RELAY 10
→
[72] Pump 1 to Line Voltage
27-73 RELAY 11
→
[73] Pump 2 to Line Voltage
27-74 RELAY 12
→
[0] Standard Relay
Extended and Advanced Cascade Controller
Option
3 Supported Configuration