6.1.5 Staging Speed, 27-3*
Parameters for configuring Master/Follower control response.
6.1.6 Auto-tune Staging Speeds, 27-30 (To be included in future versions!)
27-30 Auto-tune Staging Speeds
Option:
Function:
When enabled, the stage on and off speeds will continually be auto-tuned during operation. The
settings will be optimized in order to ensure high performance and low energy consumption. If
disabled, the speeds can be set manually.
[0]
Disabled
[1] *
Enabled
27-31 Stage On Speed (RPM)
Range:
Function:
P4-13*
[par. 4-11 – par. 4-13]
To be used if RPM is chosen.
If the lead pump is operating above Stage On Speed for the time specified in Staging Delay (par.
27-23), and a variable speed pump is available, it will be turned on.
6 How to Program
Extended and Advanced Cascade Controller
Option
6-6
MI.38.C2.22 - VLT
®
is a registered Danfoss trademark
6