FC 300 Operating Instructions
How to Programme
"
14-** Special Functions
Par.
No.
#
Parameter description
Default value
(SR = Size Related)
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
14-0* Inverter Switching
14-00Switching Pattern
[1] SFAVM
All set-ups
TRUE
-
Uint8
14-01Switching Frequency
-
All set-ups
TRUE
-
Uint8
14-03Overmodulation
[1] On
All set-ups
FALSE
-
Uint8
14-04PWM Random
[0] Off
All set-ups
TRUE
-
Uint8
14-1* Mains On/Off
14-10Mains Failure
[0] No function
All set-ups
FALSE
-
Uint8
14-11Mains Voltage at Mains Fault
SR
All set-ups
TRUE
0
Uint16
14-12Function at Mains Imbalance
[0] Trip
All set-ups
TRUE
-
Uint8
14-2* Trip Reset
14-20Reset Mode
[0] Manual reset
All set-ups
TRUE
-
Uint8
14-21Automatic Restart Time
10 s
All set-ups
TRUE
0
Uint16
14-22Operation Mode
[0] Normal operation
All set-ups
TRUE
-
Uint8
14-23Typecode Setting
-
2 set-ups
FALSE
-
Uint16
14-25Trip Delay at Torque Limit
60 s
All set-ups
TRUE
0
Uint8
14-26Trip Delay at Inverter Fault
SR
All set-ups
TRUE
0
Uint8
14-28Production Settings
[0] No action
All set-ups
TRUE
-
Uint8
14-29Service Code
0
All set-ups
TRUE
0
Int32
14-3* Current Limit Ctrl.
14-30Current Lim Cont, Proportional Gain 100 %
All set-ups
FALSE
0
Uint16
14-31Current Lim Contr, Integration Time 0.020 s
All set-ups
FALSE
-3
Uint16
14-4* Energy Optimising
14-40VT Level
66 %
All set-ups
FALSE
0
Uint8
14-41AEO Minimum Magnetisation
40 %
All set-ups
TRUE
0
Uint8
14-42Minimum AEO Frequency
10 Hz
All set-ups
TRUE
0
Uint8
14-43Motor Cosphi
SR
All set-ups
TRUE
-2
Uint16
14-5* Environment
14-50RFI Filter
[1] On
1 set-up
x
FALSE
-
Uint8
14-52Fan Control
[0] Auto
All set-ups
TRUE
-
Uint8
14-53Fan Monitor
[1] Warning
All set-ups
TRUE
-
Uint8
14-55Output Filter
[0] No Filter
1 set-up
FALSE
-
Uint8
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
56