FC 300 Operating Instructions
How to Programme
"
6-** Analog In/Out
Par.
No.
#
Parameter description
Default value
(SR = Size Related)
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6-01 Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-11 Terminal 53 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-12 Terminal 53 Low Current
0.14 mA
All set-ups
TRUE
-5
Int16
6-13 Terminal 53 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
6-14 Terminal 53 Low Ref./Feedb. Value SR
All set-ups
TRUE
-3
Int32
6-15 Terminal 53 High Ref./Feedb. Value SR
All set-ups
TRUE
-3
Int32
6-16 Terminal 53 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-2* Analog Input 2
6-20 Terminal 54 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-21 Terminal 54 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-22 Terminal 54 Low Current
0.14 mA
All set-ups
TRUE
-5
Int16
6-23 Terminal 54 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
6-24 Terminal 54 Low Ref./Feedb. Value SR
All set-ups
TRUE
-3
Int32
6-25 Terminal 54 High Ref./Feedb. Value SR
All set-ups
TRUE
-3
Int32
6-26 Terminal 54 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-3* Analog Input 3
6-30 Terminal X30/11 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-31 Terminal X30/11 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-34 Term. X30/11 Low Ref./Feedb.
Value
SR
All set-ups
TRUE
-3
Int32
6-35 Term. X30/11 High Ref./Feedb.
Value
SR
All set-ups
TRUE
-3
Int32
6-36 Term. X30/11 Filter Time Constant 0.001 s
All set-ups
TRUE
-3
Uint16
6-4* Analog Input 4
6-40 Terminal X30/12 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-41 Terminal X30/12 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-44 Term. X30/12 Low Ref./Feedb.
Value
SR
All set-ups
TRUE
-3
Int32
6-45 Term. X30/12 High Ref./Feedb.
Value
SR
All set-ups
TRUE
-3
Int32
6-46 Term. X30/12 Filter Time Constant 0.001 s
All set-ups
TRUE
-3
Uint16
6-5* Analog Output 1
6-50 Terminal 42 Output
-
All set-ups
TRUE
-
Uint8
6-51 Terminal 42 Output Min Scale
0.00 %
All set-ups
TRUE
-2
Int16
6-52 Terminal 42 Output Max Scale
100.00 %
All set-ups
TRUE
-2
Int16
6-53 Terminal 42 Output Bus Control
0.00 %
All set-ups
TRUE
-2
N2
6-54 Terminal 42 Output Timeout Preset 0.00 %
1 set-up
TRUE
-2
Uint16
6-6* Analog Output 2
6-60 Terminal X30/8 Output
-
All set-ups
TRUE
-
Uint8
6-61 Terminal X30/8 Min. Scale
0.00 %
All set-ups
TRUE
-2
Int16
6-62 Terminal X30/8 Max. Scale
100.00 %
All set-ups
TRUE
-2
Int16
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
50
MG.33.A7.02 - VLT is a registered Danfoss trademark