FC 300 Operating Instructions
How to Programme
"
4-** Limits / Warnings
Par.
No.
#
Parameter description
Default value
(SR = Size Related)
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
4-1* Motor Limits
4-10 Motor Speed Direction
-
All set-ups
FALSE
-
Uint8
4-11 Motor Speed Low Limit [RPM]
SR
All set-ups
TRUE
67
Uint16
4-12 Motor Speed Low Limit [Hz]
SR
All set-ups
TRUE
-1
Uint16
4-13 Motor Speed High Limit [RPM]
SR
All set-ups
TRUE
67
Uint16
4-14 Motor Speed High Limit [Hz]
SR
All set-ups
TRUE
-1
Uint16
4-16 Torque Limit Motor Mode
160.0 %
All set-ups
TRUE
-1
Uint16
4-17 Torque Limit Generator Mode
100.0 %
All set-ups
TRUE
-1
Uint16
4-18 Current Limit
ExpressionLimitSR
All set-ups
TRUE
-1
Uint32
4-19 Max Output Frequency
132.0 Hz
All set-ups
FALSE
-1
Uint16
4-2* Limit Factors
4-20 Torque Limit Factor Source
[0] No function
All set-ups
TRUE
-
Uint8
4-21 Speed Limit Factor Source
[0] No function
All set-ups
TRUE
-
Uint8
4-3* Motor Fb Monitor
4-30 Motor Feedback Loss Function
[2] Trip
All set-ups
TRUE
-
Uint8
4-31 Motor Feedback Speed Error
300 RPM
All set-ups
TRUE
67
Uint16
4-32 Motor Feedback Loss Timeout
0.05 s
All set-ups
TRUE
-2
Uint16
4-5* Adj. Warnings
4-50 Warning Current Low
0.00 A
All set-ups
TRUE
-2
Uint32
4-51 Warning Current High
ImaxVLT
All set-ups
TRUE
-2
Uint32
4-52 Warning Speed Low
0 RPM
All set-ups
TRUE
67
Uint16
4-53 Warning Speed High
(P413)
All set-ups
TRUE
67
Uint16
4-54 Warning Reference Low
-999999.999
All set-ups
TRUE
-3
Int32
4-55 Warning Reference High
999999.999
All set-ups
TRUE
-3
Int32
4-56 Warning Feedback Low
-999999.999
All set-ups
TRUE
-3
Int32
4-57 Warning Feedback High
999999.999
All set-ups
TRUE
-3
Int32
4-58 Missing Motor Phase Function
[1] On
All set-ups
TRUE
-
Uint8
4-6* Speed Bypass
4-60 Bypass Speed From [RPM]
SR
All set-ups
TRUE
67
Uint16
4-61 Bypass Speed From [Hz]
SR
All set-ups
TRUE
-1
Uint16
4-62 Bypass Speed To [RPM]
SR
All set-ups
TRUE
67
Uint16
4-63 Bypass Speed To [Hz]
SR
All set-ups
TRUE
-1
Uint16
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
47
MG.33.A7.02 - VLT is a registered Danfoss trademark