8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM* [0 - par. 4-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM* [0 - par. 4-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
opera-
tion
Conver-
sion in-
dex
Type
8-0* General Settings
8-01 Control Site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8-02 Control Word Source
null
All set-ups
TRUE
-
Uint8
8-03 Control Word Timeout Time
1.0 s
1 set-up
TRUE
-1
Uint32
8-04 Control Word Timeout Function
[0] Off
1 set-up
TRUE
-
Uint8
8-05 End-of-Timeout Function
[1] Resume set-up
1 set-up
TRUE
-
Uint8
8-06 Reset Control Word Timeout
[0] Do not reset
All set-ups
TRUE
-
Uint8
8-07 Diagnosis Trigger
[0] Disable
2 set-ups
TRUE
-
Uint8
8-1* Ctrl. Word Settings
8-10 Control Word Profile
[0] FC profile
All set-ups
TRUE
-
Uint8
8-13 Configurable Status Word STW
[1] Profile Default
All set-ups
TRUE
-
Uint8
8-3* FC Port Settings
8-30 Protocol
[0] FC
1 set-up
TRUE
-
Uint8
8-31 Address
1 N/A
1 set-up
TRUE
0
Uint8
8-32 FC Port Baud Rate
[2] 9600 Baud
1 set-up
TRUE
-
Uint8
8-35 Minimum Response Delay
10 ms
1 set-up
TRUE
-3
Uint16
8-36 Max Response Delay
5000 ms
1 set-up
TRUE
-3
Uint16
8-37 Max Inter-Char Delay
25 ms
1 set-up
TRUE
-3
Uint16
8-4* FC MC protocol set
8-40 Telegram selection
[1] Standard telegram 1
2 set-ups
TRUE
-
Uint8
8-5* Digital/Bus
8-50 Coasting Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-51 Quick Stop Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-52 DC Brake Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-53 Start Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-54 Reversing Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-55 Set-up Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-56 Preset Reference Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-9* Bus Jog
8-90 Bus Jog 1 Speed
100 RPM
All set-ups
TRUE
67
Uint16
8-91 Bus Jog 2 Speed
200 RPM
All set-ups
TRUE
67
Uint16
7. Parameters
FC 300 Interbus Operating Instructions
38
MG.33.H3.02 - VLT is a registered Danfoss trademark
7