5.3.2. Status Word according to Drivecom 21 Profile
(Par. 8-10 = PROFIdrive profile)
Bit
Bit value = 0
Bit value = 1
00
Not ready to switch ON Ready to switch ON
01
Switched OFF
Switched ON
02
Operation disabled
Operation enabled
03
No malfunction
Malfunction
04
Voltage disabled
Voltage enabled
05
Quick stop
Run
06
Switch on disable
Switch on enable
07
No warning
Warning
08
Reserved
09
Remote disabled
Remote enabled
10
Setpoint not reached
Setpoint reached
11
Speed limit not active
Speed limit active
12
Reserved
13
Reserved
14
Not running
Running
15
Torque limit o.k.
Torque limit exceeded
Explanation of the Bits:
Bit 00, Not ready to switch on/Ready to switch on:
Bit 00 = "0" state less than “Ready to switch on”.
Bit 00 = "1" state at least = “Ready to Switch on”.
Bit 01, Switch off/Switch on:
Bit 00 = "0" state less than “Switched on”.
Bit 00 = "1" state at least = “Switched on”.
Bit 02, Operation disable/Operation enable:
Bit 00 = "0" state less than “Operation enable”.
Bit 00 = "1" state at least = “Operation enable”.
Bit 03, No Malfunction/Malfunction:
Bit 03 = "0" means that the connection from Interbus option to is o.k.
Bit 03 = "1" means that the connection between Interbus option and has
been lost, or no is found.
Bit 04, Voltage disable/Voltage enable:
Bit 04 = "0" means that control word bit 01 = "1".
Bit 04 = "1" means that control word bit 01 = "0".
Bit 05, Quick stop/Run:
Bit 05 = "0" means that control word bit 02 = "1".
Bit 05 = "1" means that control word bit 02 = "0".
Bit 06, Start enable/Start disable:
Bit 06 = "0" state is “Switch on disable”.
Bit 06 = "1" state is “Switch on enable”.
Bit 07, No warning/Warning:
Bit 07 = "0" means that there is no warning situation.
Bit 07 = "1" means that a warning has occurred.
Bit 08, Danfoss reserved
Bit 09, Remote disable/Remote enable:
Bit 09 = "0" means that the has been stopped by means of the stop key
on the LCP, or that [Local] has been selected in par. 3-13 Reference site.
Bit 09 = "1" means that it is possible to control the converter via the serial
port.
Bit 10, Setpoint not reached/Setpoint reached:
Bit 10 = "0" means that the actual motor speed is different from the speed
reference set. This can be the case while the speed is ramped up/down
during start/stop.
Bit 10 = "1" means that the present motor speed equals the speed ref-
erence set.
Bit 11, Speed limit not active/speed limit active:
Bit 11 = "0" means that the output frequency is out of the range set in
par. 4-11/4-12 Motor Speed low Limit RPM/Hz or par. 4-13/4-14 Motor
Speed high Limit RPM/Hz.
Bit 11 = "1" means that the output frequency is within the mentioned
range.
Bit 12, Drivecom reserved
Bit 13, Drivecom reserved
Bit 14, Running/Not running:
Bit 14 = "0" means that the motor is not running.
Bit 14 = "1" means that the has a valid start signal or that the output
frequency is greater than 0 Hz.
Bit 15, Torque limit o.k./Torque limit exceeded:
Bit 15 = "0" means the torque limit received via PDC 4 is accepted and
within range.
Bit 15 = "1" means the torque limit received exceeds the limits in par.
4-15 and 4-16.