5.3. Drivecom 21 Control Profile
5.3.1. Control Word according to Drivecom 21 Profile
(Par. 8-10 = PROFIdrive profile)
Bit
Bit value = 0
Bit value = 1
00
Switch off
Switch on
01
Disable voltage
Enable voltage
02
Quick stop
Run
03
Disable operation
Enable operation
04
Disable ramp
Enable ramp
05
Freeze
Run enable
06
Ramp stop
Start
07
No function
Reset
08
Reserved
09
Reserved
10
Reserved
11
Jog 1 OFF
Jog 1 ON
12
Reserved
13
Setup select (LSB)
14
Setup select (MSB)
15
Forward
Reversing
Explanation of the Bits:
Bit 00, Switch OFF/ON:
Bit 00= "0" execute transition 2, 6 or 8.
Bit 00 = "1" execute transition 3.
Bit 01, Disable/Enable Voltage:
Bit 01= "0" execute transition 9, 10 or 12.
Bit 01 = "1" = “Enable Voltage“.
Bit 02, Quick stop/Run:
Bit 02= "0" execute transition 7, 10 or 11.
Bit 02 = "1" = Quick stop not active.
Bit 03, Disable/enable Operation:
Bit 03= "0" execute transition 5.
Bit 03 = "1" = “Enable operation“.
Bit 04, Quick-stop/ramp:
Bit 04= "0" execute transition 7 or 11, Quick stop.
Bit 04 = "1" = Enable ramp.
Bit 05, Freeze output frequency/run enable:
Bit 05 = "0" means that the given output frequency is maintained even
if the reference is changed.
Bit 05 = "1" means that the frequency converter is again able to regulate,
and the given reference is followed.
Bit 06, Ramp stop/start:
Bit 06= "0" The VLT controls the motor down to stop.
Bit 06 = "1" = Start command to the VLT is given.
Bit 07, No function/reset:
Reset of trip.
Bit 07 = "0" means that there is no reset.
Bit 07 = "1" means that a trip is reset.
Bit 08, 09 and 10:
Drivecom reserved.
Bit 11, Jog 1 OFF/ON:
Activation of pre-programmed speed in par. 8-90 Bus JOG 1. JOG 1 is
only possible if Bit 04 = "0", and bit 00 to 03 = "1".
Bit 12:
Danfoss reserved.
Bits 13/14, Selection of Setup:
Bits 13 and 14 are used for choosing among the four menu Setups in
accordance with the following table:
Bit 14
Bit 13
Setup
0
0
1
0
1
2
1
0
3
1
1
4
Bit 15, Forward/reversing:
Bit 15 = "0" leads to no reversing.
Bit 15 = "1" leads to reversing.
Note: In factory setting reversing is set to [digital] in par. 8-54
Reversing
select
.
5. How to Control the FC 300
FC 300 Interbus Operating Instructions
24
MG.33.H3.02 - VLT is a registered Danfoss trademark
5