Parameter
No.
Function
Setting
4-10
Motor speed range/direction
Both directions [2]
5-10
Digital input 18
No operation [0]
5-11
Digital input 19
Reversing [10]
5-40
Function relay
Control word bit 11 [36]
Control word bit 12 [37]
8-03
Control word timeout time
1.0 sec
8-04
Control word timeout function
Stop [2]
8-10
Control word profile
FC Profile
8-50
Coasting select
Bus [1]
8-51
Quick-stop select
Bus [1]
8-52
DC-brake select
Bus [1]
8-53
Start select
Bus [1]
8-54
Reversing select
Logic AND [2]
8-55
Set-up select
Bus [1]
8-56
Preset reference select
Bus [1]
10-01
Baud rate select
- set to match other DeviceNet stations
10-02
MAC ID
- set desired station address
10-10
Process data type selection
Instance 101/151 [1]
10-12
Process Data Config Read
PCD 3: Torque
PCD 4: Digital input
7.1.1. Example of PLC Programming
In this example Instance 101/151 is placed in the following Input/Output address:
Input ad-
dress
0.0-0.15
0.16-0.31 1.0-1.15
1.16-1.31
Set-up
Status
word
MAV
Motor tor-
que
Digital in-
put
7. Application Examples
FC 100/ 200/ 300 DeviceNet
70
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
7