Select the control source in Instance 21/71 and 20-70.
[0]
*
Off
Enables control via analog/digital inputs.
[1]
On
enable control via the fieldbus.
10-20 COS Filter 1
Range:
Function:
0
*
[0 - FFFF]
Sets up the filter mask for the status word. When operating in
COS (Change-Of-State), it is possible to filter out bits in the sta-
tus word that should not be sent if they change.
10-21 COS Filter 2
Range:
Function:
65535
*
[0 - 65535]
Sets up the filter mask for the Main Actual Value. When oper-
ating in COS (Change-Of-State), it is possible to filter out bits in
the Main actual value that should not be sent if they change.
10-22 COS Filter 3
Range:
Function:
65535
*
[0 - 65535]
Sets up the filter mask for PCD 3. When operating in COS
(Change-Of-State), it is possible to filter out bits in PCD 3 that
should not be sent if they change.
10-23 COS Filter 4
Range:
Function:
65535
*
[0 - 65535]
Sets up the filter mask for PCD 4. When operating in COS
(Change-Of-State), it is possible to filter out bits in PCD 4 that
should not be sent if they change.
10-30 Array Index
Range:
Function:
0
*
[0 - 255]
View array parameters. This parameter is valid only when a De-
viceNet fieldbus is installed.
10-31 Store Data Values
Option:
Function:
[0]
*
Off
[1]
Store edit set-up
[2]
Store all set-ups
This parameter is used to activate a function that stores all pa-
rameter values in the non-volatile memory thus retaining
changed parameter values at power down.
-
'*Off:
The store function is inactive.
-
Store edit set-up:
All parameter values in the set-up selected
will be stored in the non-volatile memory.
The value returns to
Off
when all values have been stored.
6. Parameters
FC 100/ 200/ 300 DeviceNet
64
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
6