319A 

Manual RS8EB102 © Danfoss 09-2005 

3

Survey of functions

Function 

Para- 

meter

Parameter by operation via 

data communication

Normal display
The temperature sensor registers the discharge gas temperature.

The value is shown in the display.

-

Temperature

The valve’s actual opening degree can be displayed by giving the lower button a brief 

push (1s). Cf. also o17.

-

OD %

Reference

Temperature control

Reference

The liquid injection starts when the set value is passed.

Push both buttons simultaneously to set the setpoint.

-

Temperature Ref

Start/stop of regulation

With this setting the regulation can be started and stopped. 

Start/stop can also be performed with the external contact function.

Regulation is stopped if just one of them is OFF.

r12

Main Switch

Alarm
The controller can give alarm in different situations.

When there is an alarm the three lowest LED’s at the front of the controller will flash, 

and the alarm relay is cut in. See also A19.
Alarm limit

A temperature limit can be set where the alarm is to be activated.

A16

Limit Alarm

Time delay for alarm

When the temperature value is exceeded a timer function will start. The alarm will not 

become activated until the set time delay has been passed.

The time delay is set in seconds.

A17

Limit Alm. delay

Activation of the alarm relay

Set here whether the alarm relay is to be activated when the time delay has been 

passed:

0: Alarm relay active

1: Alarm relay not active

A19

Alarm type 

(With setting = 0 the alarm is also 

transmitted via the data communica-

tion)

With data communication the impor-

tance of the individual alarms can be 

defined. Setting is carried out in the 

“Alarm destinations” menu.

Control parameters

Control Settings

P - band

If the value is reduced the regulating range will be reduced. (The P-band will be over 

the reference).

n04

Kp factor

I: Integration time Tn

The I-link can be made passive by setting the value at max. (600s)

(If the Tn value is increased the regulation becomes slower).

n05

Tn sec.

Periode time

The valve is operated with pulses of a given length. The length depends on the open-

ing degree required. If a large opening degree is required, the pulse will last for an 

entire period time. A period time will thus comprise both open and closed valve.

n13

Period time

Miscellaneous

Miscellaneous

Address

If the controller is built into a network with data communication, it must have an 

address, and the master gateway of the data communication must then know this 

address.

These settings can only be madewhen a data communication modulehas been 

mounted in the controller and the installation of the data communication cable has 

been completed.

This installation is mentioned in a separate document “RC8AC”..

Following installation of a data com-

munication module, the controller can 

be operated on a par with the other 

controllers in ADAP-KOOL® refrigera-

tion controls. 

The address is set between 1 and 60 (119)

o03

-

The address is sent to the gateway when the menu is set in pos. ON

(The setting will automatically change back to Off after a few seconds.)

o04

-

Frequency

Set the net frequency.

o12

50 / 60 Hz

(50=0, 60=1)

Summary of Contents for EKC 319A

Page 1: ...Temperature controller for limitation for the discharge gas temperature EKC 319A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...ion valve type AKV or a type AKVA for NH3 is used The capacity requirement is determined by the size of the valve If the compressor is provided with a connection for liquid injection a pulse solenoid...

Page 3: ...With setting 0 the alarm is also transmitted via the data communica tion With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm destinatio...

Page 4: ...o18 Service Service A number of controller values can be printed for use in a service situation Read discharge gas temperature u01 Temperature Read the temperature reference u02 Temperature ref Read...

Page 5: ...the buttons and select the new value 5 Push both buttons again to conclude the setting SW 1 1x Function Para meter Min Max Fac setting Normal display Read the measured discharge gas temperature C If...

Page 6: ...brations Enclosure IP 20 Weight 300 g Montage DIN Rail Display LED 3 digits Terminals max 2 5 mm2 multicore Approvals EU Low Voltage Directive and EMC demands re CE marking complied with LVD tested ac...

Page 7: ...e upload all the collected tempera ture values once a day Example of menu display Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 8: ...t such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respecitve companies Danfoss and Danf...

Reviews: