EKC 

319A

Introduction

Application

The controller limits the pressure gas temperature in compressors 

by opening up for liquid injection in the suction line.

System

A temperature sensor will register the pressure gas temperature.

If the temperature reaches the set temperature value, opening of 

the valve will be commenced.

A PI regulation will adapt the opening degree of the valve so that 

the temperature will be limited.

Temperature sensor

Type AKS 21 can be used. It can stand the high temperature.

Valve 

If the liquid injection is carried out directly in the suction line an 

expansion valve type AKV, or a type AKVA (for NH

3

), is used. The 

capacity requirement is determined by the size of the valve. If the 

compressor is provided with a connection for liquid injection a 

pulse solenoid valve type EVRP is used in the liquid supply.

Alarm function

The controller will sound an alarm if the set alarm limit is ex-

ceeded.

The alarm will activate the alarm relay.

Extra options

PC operation

The controller can be provided with data communication, so that 

it may be hooked up with other products in the ADAP-KOOL® 

range of refrigeration controls. Operation, moni toring and data 

collection can then be performed from a PC - either in situ or at a 

service company.

EKC 319A

Literature survey:

Manual for EKC 319A .................................................................RS8EB..

Instructions for EKC 319A ........................................................RI8HY..

Installation guide, "Data communication link

  for ADAP-KOOL® " .................................................................RC8AC..

Summary of Contents for EKC 319A

Page 1: ...Temperature controller for limitation for the discharge gas temperature EKC 319A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...ion valve type AKV or a type AKVA for NH3 is used The capacity requirement is determined by the size of the valve If the compressor is provided with a connection for liquid injection a pulse solenoid...

Page 3: ...With setting 0 the alarm is also transmitted via the data communica tion With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm destinatio...

Page 4: ...o18 Service Service A number of controller values can be printed for use in a service situation Read discharge gas temperature u01 Temperature Read the temperature reference u02 Temperature ref Read...

Page 5: ...the buttons and select the new value 5 Push both buttons again to conclude the setting SW 1 1x Function Para meter Min Max Fac setting Normal display Read the measured discharge gas temperature C If...

Page 6: ...brations Enclosure IP 20 Weight 300 g Montage DIN Rail Display LED 3 digits Terminals max 2 5 mm2 multicore Approvals EU Low Voltage Directive and EMC demands re CE marking complied with LVD tested ac...

Page 7: ...e upload all the collected tempera ture values once a day Example of menu display Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 8: ...t such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respecitve companies Danfoss and Danf...

Reviews: