background image

Manual RS8EB102 © Danfoss 09-2005 

EKC 

319A

Selection of display

The normal display can be defined to show either:

0: Discharge gas temperature

1: Opening degree of valve

Later during the regulation:

If the second display is to be read, the controller’s lowermost button must be 

activated briefly.

After five seconds the normal display will reappear.

o17

Display

Manual control of outputs

In connection wit service the alarm relay and the valve output can be put in pos. ON. 

But not until regulation has been stopped.

OFF:  No override

1: Valve output is ON

2. Alarm relay is activated (terminals 12 and 13 will be cutin)

o18

-

Service

Service

A number of controller values can be printed for use in a service situation
Read discharge gas temperature

u01

Temperature

Read the temperature reference

u02

Temperature ref

Read status of input DI (start/stop input)

u10

DI

Read valve’s opening degree

u24

OD %

--

DO1 limit alarm

Read status of alarm relay

ON is operating status with alarm

Operating status
Operating status of the controller can be called forth in the display.

Push briefly (1s) the upper button. If there is a status code, it will be shown on the dis-

play. (Status codes have lower priority than alarm codes. In other words, you cannot 

see a status code, if there is an active alarm).

The individual status codes have the following meanings:

EKC Status

(0 = regulation)

S10: The regulation stopped by the internal or external start/ stop

10

Summary of Contents for EKC 319A

Page 1: ...Temperature controller for limitation for the discharge gas temperature EKC 319A User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...ion valve type AKV or a type AKVA for NH3 is used The capacity requirement is determined by the size of the valve If the compressor is provided with a connection for liquid injection a pulse solenoid...

Page 3: ...With setting 0 the alarm is also transmitted via the data communica tion With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm destinatio...

Page 4: ...o18 Service Service A number of controller values can be printed for use in a service situation Read discharge gas temperature u01 Temperature Read the temperature reference u02 Temperature ref Read...

Page 5: ...the buttons and select the new value 5 Push both buttons again to conclude the setting SW 1 1x Function Para meter Min Max Fac setting Normal display Read the measured discharge gas temperature C If...

Page 6: ...brations Enclosure IP 20 Weight 300 g Montage DIN Rail Display LED 3 digits Terminals max 2 5 mm2 multicore Approvals EU Low Voltage Directive and EMC demands re CE marking complied with LVD tested ac...

Page 7: ...e upload all the collected tempera ture values once a day Example of menu display Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 8: ...t such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respecitve companies Danfoss and Danf...

Reviews: