Danfoss EKC 202B Manual Download Page 9

EKC 

202 

302 

Manual RS8DZ702 © Danfoss 03-2012 

9

Alarm

Alarm settings

The controller can give alarm in different situations. When there is an alarm all the light-emitting 

diodes (LED) will flash on the controller front panel, and the alarm relay will cut in.

With data communication the importance 

of the individual alarms can be defined. 

Setting is carried out in the “Alarm destina

-

tions” menu. 

Alarm delay 

(short alarm delay)

If one of the two limit values is exceeded, a timer function will commence. The alarm will not 

become active until the set time delay has been passed. The time delay is set in minutes.

A03

Alarm delay

Time delay for door alarm

The time delay is set in minutes.

The function is defined in o02.

A04

DoorOpen del

Time delay for cooling 

(long alarm delay)

This time delay is used during start-up, during defrost, immediately after a defrost.

There will be change-over to the normal time delay (A03) when the temperature has dropped 

below the set upper alarm limit.

The time delay is set in minutes.

A12

Pulldown del

Upper alarm limit

Here you set when the alarm for high temperature is to start. The limit value is set in °C (absolute 

value). The limit value will be raised during night operation. The value is the same as the one set 

for night setback, but will only be raised if the value is positive.

The limit value will also be raised in connection with reference displacement r39.

A13

HighLim Air

Lower alarm limit

Here you set when the alarm for low temperature is to start. The limit value is set in °C (absolute 

value).

The limit value will also be raised in connection with reference displacement r39.

A14

LowLim Air

Delay of a DI alarm

A cut-out/cut-in input will result in alarm when the time delay is passed. The function is defined 

in o02.

A27

AI.Delay DI

High alarm limit for condenser temperature

If the S5 sensor is used for monitoring the condenser’s temperature you must set the value at 
which the alarm is to become activated. The value is set in °C.

The definition of S5 as condenser sensor is accomplished in o70. The alarm is zeroset again 10 K 

below the set temperature.

A37

Condtemp Al.

Reset alarm

Compressor

Compressor control

The compressor relay works in conjunction with the thermostat. When the thermostat calls for 

refrigeration will the compressor relay be operated.

Running times

To prevent irregular operation, values can be set for the time the compressor is to run once it has 

been started. And for how long it at least has to be stopped.

The running times are not observed when defrosts start.

Min. ON-time (in minutes)

c01

Min. On time

Min. OFF-time (in minutes)

c02

Min. Off time

Reversed relay function for compressor relay

0: Normal function where the relay cuts in when refrigeration is demanded

1: Reversed function where the relay cuts out when refrigeration is demanded (this wiring pro

-

duces the result that there will be refrigeration if the supply voltage to the controller fails). 

c30

Cmp relay NC

External relay (only EKC 302)

Here it is possible to force the build in relays to connect in the voltage's zero crossing. The life

-

time of the relays is increased, or the load can be increased.

The function should not be activated if contactors are connected to one or more of the control

-

ler's relays. This will result in a reduction of the contactors lifetime.

0: The load is connected directly to the controller's relays (zero-crossing activated)

Relay contact and controller supply 

must

 use same phase.

1: The controller's relay must draw a external contactor (zero-crossing cancelled)

c70

Ext. Relay

Summary of Contents for EKC 202B

Page 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Page 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Page 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Page 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Page 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Page 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Page 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Page 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Page 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Page 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Page 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Page 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Page 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Page 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Page 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Page 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Page 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Page 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Page 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Page 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Reviews: