Miscellaneous

Miscellaneous

Delay of output signal after start-up

After start-up or a power failure the controller’s functions can be delayed so that overloading of 

the electricity supply network is avoided. 

Here you can set the time delay.

o01

DelayOfOutp.

Digital input signal - DI

The controller has a digital input which can be used for one of the following functions:

Off: The input is not used

1) Status display of a contact function

2

) Door function. When the input is open it signals that the door is open. The refrigeration and 

the fans are stopped. When the time setting in “A04” is passed, an alarm will be given and 

refrigeration will be resumed.

3) Door alarm. When the input is open it signals that the door is open. When the time setting in 

“A04” is passed, there will be alarm.

4) Defrost. The function is started with a pulse pressure. The controller will register when the DI 

input is activated. The controller will then start a defrost cycle. If the signal is to be received by 

several controllers it is important that ALL connections are mounted the same way (DI to DI 

and GND to GND).

5) Main switch. Regulation is carried out when the input is short-circuited, and regulation is 

stopped when the input is put in pos. OFF.

6) Night operation. When the input is short-circuited, there will be regulation for night opera

-

tion.

7) Reference displacement when DI1 is short-circuited. Displacement with “r40”.

8) Separate alarm function. Alarm will be given when the input is short-circuited.

9) Separate alarm function. Alarm will be given when the input is opened.  (For 8 and 9 the time 

delay is set in A27)

10) Case cleaning. The function is started with a pulse pressure. Cf. also description on page 4.

11) Inject on/off. Off when DI is open.

o02

DI 1 Config.

Definition takes place with the numerical 

value shown to the left.

(0 = off)

DI state

(Measurement)

The DI input’s present status is shown here. 

ON or OFF.

Address

If the controller is built into a network with data communication, it must have an address, and 

the

 

master gateway of the data communication must then know this address.

The installation of the data communication cable has been mentioned in a separate 

document “RC8AC”.

After installation of data communication 

the controller can be operated on an equal 

footing with the other controllers in ADAP-

KOOL® refrigeration controls.

The address is set between 1 and 240, gateway determined

o03

The address is sent to the system manager when the menu o04 is set to 'ON', or when the system 

manager's scanning function is activated. (o04 is only to be used if the data communication is 

LON.)

o04

Access code 1 (Access to all settings)

If the settings in the controller are to be protected with an access code you can set a numerical 
value between 0 and 100. If not, you can cancel the function with setting 0. (99 will always give 
you access).

o05

-

Sensor type

Normally a Pt 1000 sensor with great signal accuracy is used. But you can also use a sensor with 

another signal accuracy. That may either be a PTC sensor (1000 ohm at 25°C) or an NTC sensor 

(5000 Ohm at 25°C).

All the mounted sensors must be of the same type.

o06

SensorConfig

Pt = 0

PTC = 1

NTC = 2

Display step

Yes: Gives steps of 0.5°

No: Gives steps of 0.1°

o15

Disp. Step = 0.5

Max. standby time after coordinated defros

t

When a controller has completed a defrost it will wait for a signal which tells that the refrigera

-

tion may be resumed. If this signal fails to appear for one reason or another, the controller will 

itself start the refrigeration when this standby time has elapsed.

o16

Max HoldTime

Configuration of light function 

1) The relay cuts in during day operation

2) The relay to be controlled via data communication

3) The relay to be controlled by the door switch defined in either o02 where the setting is 

selected to either 2 or 3. When the door is opened the relay will cut in. When the door is closed 

again there will be a time delay of two minutes before the light is switched off.

o38

Light config

Activation of light relay

The light relay can be activated here (if 038=2)

o39

Light remote

Case cleaning

The status of the function can be followed here or the function can be started manually.

= Normal operation (no cleaning)

= Cleaning with fans operating. All other outputs are Off.

2

 = Cleaning with stopped fans. All outputs are Off.

If the function is controlled by a signal at the DI input, the relevant status can be seen here in the 

menu.

o46

Case clean

Access code 2 (Access to adjustments)

There is access to adjustments of values, but not to configuration settings. If the settings in the 

controller are to be protected with an access code you can set a numerical value between 0 and 

100. If not, you can cancel the function with setting 0. If the function is used, access code 1 (o05) 

must also 

be used.

o64

-

Summary of Contents for EKC 202B

Page 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Page 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Page 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Page 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Page 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Page 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Page 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Page 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Page 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Page 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Page 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Page 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Page 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Page 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Page 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Page 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Page 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Page 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Page 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Page 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Reviews: