Copy the controller’s present settings (EKC 202 only)

With this function the controller’s settings can be transferred to a programming key. The key 

can contain up to 25 different sets. Select a number. All settings except for Address (o03) will be 

copied. When copying has started the display returns to o65. After two seconds you can move 

into the menu again and check whether the copying was satisfactory.

Showing of a negative figure spells problems. See the significance in the Fault Message section.

o65

-

Copy from the programming key (EKC 202 only)

This function downloads a set of settings earlier saved in the controller. Select the relevant 

number.

All settings except for Address (o03) will be copied. When copying has started the display 

returns to o66. After two seconds you can move back into the menu again and check whether 

the copying was satisfactory. Showing of a negative figure spells problems. See the significance 

in the Fault Message section.

o66

-

Save as factory setting

With this setting you save the controller’s actual settings as a new basic setting (the earlier fac

-

tory settings are overwritten).

o67

-

Other application for S5 sensor

Maintain the setting at 0 if the sensor has been defined as defrost sensor in D10. If D10 has been 

set at 0 or 2 the S5 input can be used as product sensor or condenser sensor. Here you define 

which: 

0: Defrost sensor

1: Product sensor

2: Condenser sensor with alarm

o70

S5 Config

Relay 4

Here you define the application for relay 4:

1: Defrost (EKC 202A / 302A) or Light (EKC 202C) 

2: Alarm

o72

DO4 Config

- - - Night Setback

0=Day

1=Night

Service

Service

Temperature measured with S5 sensor

u09

S5 temp.

Status on DI input. on/1=closed

u10

DI1 status

Status on night operation (on or off) 1=night operation

u13

Night Cond.

Read the present regulation reference

u28

Temp. ref.

* Status on relay for cooling

u58

Comp1/LLSV

* Status on relay for fan

u59

Fan relay

* Status on relay for defrost

u60

Def. relay

* Temperature measured with Sair sensor

u69

Sair temp

* Status on relay 4 (alarm, defrost or light function)

u71

DO4 status

*) Not all items  will be shown. Only the function belonging to the selected application can be 

seen.

Summary of Contents for EKC 202B

Page 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Page 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Page 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Page 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Page 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Page 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Page 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Page 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Page 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Page 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Page 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Page 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Page 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Page 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Page 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Page 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Page 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Page 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Page 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Page 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Reviews: