Defrost on demand – aggregate refrigeration time

Set here is the refrigeration time allowed without defrosts. If the time is passed, a defrost will be 

started.

With setting = 0 the function is cut out.

d18

MaxTherRunT

Defrost on demand – S5 temperature

The controller will follow the effectivity of the evaporator, and via internal calculations and 

measurements of the S5 temperature it will be able to start a defrost when the variation of the 

S5 temperature becomes larger than required.

Here you set how large a slide of the S5 temperature can be allowed. When the value is passed, 

a defrost will start.
The function can only be used in 1:1 systems when the evaporating temperature will become 
lower to ensure that the air temperature will be maintained. In central systems the function 
must be cut out.

With setting = 20 the function is cut out

d19

CutoutS5Dif.

If you wish to see the temperature at the S5 sensor, push the controller’s lowermost button.

Defrost temp.

If you wish to start an extra defrost, push the controller’s lowermost button for four seconds.

You can stop an ongoing defrost in the same way

Def Start

Here you can start a manual defrost.

Hold After Def

Shows ON when the controller is

operating with coordinated defrost.
Defrost State

Status on defrost

1= pump down / defrost

Fan

Fan control

Fan stopped at cut-out compressor

Here you can select whether the fan is to be stopped when the compressor is cut out

F01

Fan stop CO 

(Yes = Fan stopped)

Delay of fan stop when compressor is cut out

If you have chosen to stop the fan when the compressor is cut out, you can delay the fan stop 

when the compressor has stopped.

Here you can set the time delay.

F02

Fan del. CO 

Fan stop temperature

The function stops the fans in an error situation, so that they will not provide power to the appli

-

ance. If the defrost sensor registers a higher temperature than the one set here, the fans will be 

stopped. There will be re-start at 2 K below the setting.

The function is not active during a defrost or start-up after a defrost.

With s50°C the function is interrupted.

F04

FanStopTemp.

Real-time clock

The controller (EKC 202) can accommodate one insertion module which may either be a data 

communication module or a battery module for the real-time clock.

The battery module is used in conjunction with the real-time clock and will keep the clock going 

during lengthy power failures.

(Times cannot be set via data communica

-

tion. Settings are only relevant when there 

is no data communication).

Real-time clock

 

You can set up to six individual times for defrost starts for each 24-hour period. There is also a 

date indication used for registration of temperature measurements.
Defrost start, hour setting

t01-t06

Defrost start, minute setting (1 and 11 belong together, etc.)

When all t01 to t16 equal 0 the clock will not start defrosts.

t11-t16

Clock: Hour setting

t07

Clock: Minute setting

t08

Clock: Date setting

t45

Clock: Month setting

t46

Clock: Year setting

t47

Summary of Contents for EKC 202B

Page 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Page 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Page 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Page 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Page 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Page 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Page 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Page 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Page 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Page 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Page 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Page 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Page 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Page 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Page 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Page 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Page 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Page 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Page 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Page 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Reviews: