Start-up:
Regulation starts when the voltage is on.
1 Go through the survey of factory settings. Make any necessary changes
in the respective parameters.
2 For network. Set the address in o03 and then transmit it to the gateway/
system unit with setting o04.
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.
o46
0
2
0
Access code 2 (partly access)
o64
0
100
0
EKC 202 only. Save the controllers present settings to the programming key. Select your
own number.
o65
0
25
0
EKC 202 only. Load a set of settings from the programming key (previously saved via o65
function)
o66
0
25
0
Replace the controllers factory settings with the present settings
o67
OFF
On
OFF
Re alternative application for the S5 sensor (maintain the setting at 0 if it is used as
defrost sensor, otherwise 1 = product sensor and 2 = condenser sensor with alarm)
o70
0
2
0
Select application for relay 4: 1=defrost/light, 2= alarm
o72
defrost /
Alarm
Light /
Alarm
1
2
2
Service
Temperature measured with S5 sensor
u09
Status on DI1 input. on/1=closed
u10
Status on night operation (on or off) 1=closed
u13
Read the present regulation reference
u28
Status on relay for cooling (Can be controlled manually, but only when r12=-1)
u58
Status on relay for fans (Can be controlled manually, but only when r12=-1)
u59
Status on relay for defrost. (Can be controlled manually, but only when r12=-1)
u60
Temperature measured with Sair sensor
u69
Status on relay 4 (alarm, defrost, light). (Can be controlled manually, but only when
r12=-1)
u71
Fault code display
Alarm code display
Status code display
E1
Fault in controller
A 1
High temperature alarm
S0
Regulating
E6
Change b check clock
A 2
Low temperature alarm
S1
Waiting for end of the coordinated defrost
E 27
S5 sensor error
A 4
Door alarm
S2
ON-time Compressor
E 29
Sair sensor error
A 5
Max. Hold time
S3
OFF-time Compressor
A 15
DI 1 alarm
S4
Drip-off time
A 45
Standby mode
S10
Refrigeration stopped by main switch
A 59
Case cleaning
S11
Refrigeration stopped by thermostat
A 61
Condenser alarm
S14
Defrost sequence. Defrosting
S15
Defrost sequence. Fan delay
S16
Refrigeration stopped because of open DI
input
S17
Door open (open DI input)
S20
Emergency cooling
S25
Manual control of outputs
S29
Case cleaning
S32
Delay of output at start-up
non
The defrost temperature cannot be dis
-
played. There is stop based on time
-d-
Defrost in progress / First cooling after
defrost
PS
Password required. Set password
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon nect the
supply voltage