Danfoss EKC 202B Manual Download Page 6

Manual  RS8DZ702  ©  Danfoss  03-2012                                                                               EKC 202 / 302 

Menu survey

Parameters

Controller

Min.-

value

Max.-

value

Factory 

setting

Actual 

setting

Function

 Codes

EKC 

202A / 

302A

EKC 

202B 

/302B

EKC 

202C

Normal operation

Temperature (set point)

---

-50°C

50°C

2°C

Thermostat

Differential

r01

0,1 K

20 K

2 K

Max. limitation of set point setting

r02

-49°C

50°C

50°C

Min. limitation of set point setting

r03

-50°C

49°C

-50°C

Adjustment of temperature indication

r04

-20 K

20 K

0.0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from Sair

r09

-10 K

10 K

0 K

Manual service(-1), stop regulation(0), start regulation (1)

r12

-1

1

1

Displacement of reference during night operation

r13

-10 K

10 K

0 K

Activation of reference displacement r40

r39

OFF

on

OFF

Value of reference displacement (activation by r39 or DI)

r40

-50 K

50 K

0 K

Alarm

Delay for temperature alarm

A03

0 min

240 min

30 min

Delay for door alarm

A04

0 min

240 min

60 min

Delay for temperature alarm after defrost

A12

0 min

240 min

90 min

High alarm limit

A13

-50°C

50°C

8°C

Low alarm limit

A14

-50°C

50°C

-30°C

Alarm delay DI1

A27

0 min

240 min

30 min

High alarm limit for condenser temperature (o70)

A37

0°C

99°C

50°C

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Compressor relay must cutin and out inversely (NC-function)

c30

0 / OFF

1 / on

0 / OFF

External relays (Zero crossing control – only EKC 302)

Must be 'ON' when connecting to external relays

c70

OFF

On

On

Defrost

Defrost method (none/EL/gas)

d01

no

gas

EL

Defrost stop temperature

d02

0°C

25°C

6°C

Interval between defrost starts

d03

0 hours

48 hours

8 hours

Max. defrost duration

d04

0 min

180 min

45 min

Displacement of time on cutin of defrost at start-up

d05

0 min

240 min

0 min

Drip off time

d06

0 min

60 min

0 min

Delay for fan start after defrost

d07

0 min

60 min

0 min

Fan start temperature

d08

-15°C

0°C

-5°C

Fan cutin during defrost

0: Stopped

1: Running

2: Running during  pump down and defrost

d09

0

2

1

Defrost sensor (0=time, 1=S5, 2=Sair)

d10

0

2

0

Max. aggregate refrigeration time between two defrosts

d18

0 hours

48 hours

0 hours

Defrost on demand - S5 temperature’s permitted variation during frost build-up. On 

central plant choose 20 K (=off)

d19

0 K

20 K

20 K

Fans

Fan stop at cutout compressor

F01

no

yes

no

Delay of fan stop

F02

0 min

30 min

0 min

Fan stop temperature (S5)

F04

-50°C

50°C

50°C

Real time clock

Six start times for defrost. 

Setting of hours.

 

0=OFF

t01-t06

0 hours

23 hours

0 hours

Six start times for defrost.

Setting of minutes.

0=OFF

t11-t16

0 min

59 min

0 min

Clock - Setting of hours

t07

0 hours

23 hours

0 hours

Clock - Setting of minute

t08

0 min

59 min

0 min

Clock - Setting of date

t45

1

31

1

Clock - Setting of month

t46

1

12

1

Clock - Setting of year

t47

0

99

0

Miscellaneous

Delay of output signals after start-up

o01

0 s

600 s

5 s

Input signal on DI1. Function:

0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm 

when open. 4=defrost start (pulse-pressure).  5=ext.main switch. 6=night operation 

7=change reference (r40 will be activated) 8=alarm function when closed. 9=alarm func

-

tion when open. 10=case cleaning (pulse pressure). 11=Inject off when open.

o02

0

11

0

Network address

o03

0

240

0

On/Off switch (Service Pin message)

o04

OFF

ON

OFF

Access code 1 (all settings)

o05

0

100

0

Used sensor type (Pt /PTC/NTC)

o06

Pt

ntc

Pt

Display step = 0.5 (normal 0.1 at Pt sensor)

o15

no

yes

no

Max hold time after coordinated defrost

o16

0 min

60 min

20

Configuration of light function (relay 4)

1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI-

function, when DI is selected to door function or to door alarm

o38

1

3

1

Activation of light relay (only if o38=2)

o39

OFF

ON

OFF

EKC 202: SW = 1.3x

EKC 302: SW = 1.0x

Summary of Contents for EKC 202B

Page 1: ...Controller for temperature control EKC 202A B C and EKC 302A B Manual...

Page 2: ...t the application determines which Refrigeration compressor or solenoid valve Defrost Fan Alarm Light The different applications are described on next page Advantages Integrated refrigeration technica...

Page 3: ...of compressor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital in...

Page 4: ...eration Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase Via three p...

Page 5: ...the new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operat...

Page 6: ...lay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 15 C 0 C 5 C Fan cutin during defrost 0 Stopped 1 Running 2 Running during pump down and defrost d09 0 2 1 Defrost sens...

Page 7: ...on relay for fans Can be controlled manually but only when r12 1 u59 Status on relay for defrost Can be controlled manually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on...

Page 8: ...s temperature showing If the temperature at the products and the temperature received by the controller are not identi cal an offset adjustment of the shown display temperature can be carried out r04...

Page 9: ...nput will result in alarm when the time delay is passed The function is defined in o02 A27 AI Delay DI High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condenser...

Page 10: ...me between defrosts If a defrost start via data communication does not take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communic...

Page 11: ...ct whether the fan is to be stopped when the compressor is cut out F01 Fan stop CO Yes Fan stopped Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor i...

Page 12: ...ooting with the other controllers in ADAP KOOL refrigeration controls The address is set between 1 and 240 gateway determined o03 The address is sent to the system manager when the menu o04 is set to...

Page 13: ...tion o66 Save as factory setting With this setting you save the controller s actual settings as a new basic setting the earlier fac tory settings are overwritten o67 Other application for S5 sensor Ma...

Page 14: ...Case cleaning A61 Condenser alarm Cond alarm E1 Faults in the controller EKC error E6 Fault in real time clock Check the battery reset the clock E27 Sensor error on S5 S5 error E29 Sensor error on Sa...

Page 15: ...em Manager Function via data communication Functions to be used in the gateway s override function Used parameter in EKC 202 and EKC 302 Start of defrosting Defrost control Time schedule Def start Coo...

Page 16: ...ral connections are Refrigeration The contact will cut in when the controller demands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and w...

Page 17: ...r than a display on data communication The distance to the display must not exceed 200 m An address has to be set in o03 0 can not be used The display will self find the controller address Extenal dis...

Page 18: ...odule that will protect the clock in case of lengthy power failure 0848577 EKA 182A Copy key EKC EKC 084B8567 Temperature sensors please refer to lit no RK0YG Type Function Supply voltage Code no EKC...

Page 19: ...ed MODBUS Can be expanded with LON or MODBUS via insert card Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density EKC 202 I...

Page 20: ...serves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specif...

Reviews: