background image

Manual 

EIM 316/336 interface application for setup and configuration of MMIMyK

7

© Danfoss A/S (AC-MCI/sw), 2014-03                                    

DKRCC.PS.RQ0.C2.02 / 520H8422

Group1

Group2

Parameter

Description

Min

Max

Default

Units

Level

Notes

LOC

2

LTR

LOC Trig

0

100

95

%

2

LRe

LOC Reset

0

100

85

%

2

LTm

LOC Timer

0

7200

3600

s

2

LST

LOC SH Trig

0.0

50.0

20.0

K

2

Setup

0

Modbus

3

o03

Unit Addr

1

240

165

3

UA2

Unit Addr 2

1

240

164

3

MBa

MB Baud

0

2

1

3

96;192;384

MPa

MB Parity

0

2

2

3

NO;ODD;EVEN

MSB

MB StopB

1

2

1

3

--;1;2

Valve

2

MST

Max steps

100

1000

384

3

MSS

Max steps/sec

5

300

31

3

BKS

Start backlash

1

100

10

%

2

BKL

Backlash

0

100

20

2

COD

Comp. dir.

1

2

1

3

UP;DOWN

MCU

Motor current

0

300

150

3

Regfrigerant

2

RFG

Refrigerant

0

37

23

2

1 : R12 

2 : R22 

3 : R134a 

4 : R502 

5 : R717

6 : R13 

7 : R13b1 

8 : R23 

9 : R500 

10 : R503 

11 : R114 

12 : R142b

13 : User D

14 : R32 

15 : R227 

16 : R401A 

17 : R507 

18 : R402A 

19 : R404A 

20 : R407C 

21 : R407A 

22 : R407B 

23 : R410A 

24 : R170

25 : R290 

26 : R600

27 : R600a 

28 : R744 

29 : R1270 

30 : R417A 

31 : R422A

32 : R413A

33 : R422D

34 : R427A

35 : R438A

36 : Opteon 

XP10

37 : R407F

RF1

Rfg. fac. A1

8000

12000

10428

3

RF2

Rfg. fac. A2

-4000

-1000

-2255

3

RF3

Rfg. fac. A3

1000

3000

2557

3

Sensors

2

r09

Adjust S2

-10.0

10.0

0.0

K

2

o20

Min transducer 

press

0

1.0

0.0

Bar

(abs)

2

o21

Max transducer 

press

1

200

0.0

Bar

(abs)

2

System

0

LBO

Limited list (BO)

0

1

0

0

OFF;ON

HWM

HW main switch

0

1

0

2

OFF;ON

F2U

Factory to user

0

1

0

3

OFF;ON

U2F

User to factory

0

1

0

3

OFF;ON

TSA

Sampling time

1

10

1

3

MOS

Manual OD as 

steps

0

1

0

3

Enable the manual OD in o45 to be 

entered as halfsteps. 

MyK Setup

0

System

0

add

Active EIM Addr

0

254

165

0

bAU

Serial baudrate 

0

8

6

MB

0

0;12;24;48;96;144;192;288;384

COM

Serial settings 

0

2

1

MB

0

8N1;8E1;8N2

Passwords

1

System

1

L01

Level 1 psswd

0

9999

1000

1

L02

Level 2 psswd

0

9999

2000

2

L03

Level 3 psswd

0

9999

3000

3

6.5 Parameters

 (continued)

Summary of Contents for EIM 316

Page 1: ...e Features Configure EIM parameter Display setting Read out of status and parameters Manual control of the valve This application allows the user to configure the EIM316 336 parameters and display set...

Page 2: ...ion 4 2 References 4 3 Loading the application into the MyK 4 3 1 MyKManager 4 3 2 Copying 4 4 Connecting the MyK 4 5 Starting the application 5 6 Using the application 5 6 1 The main screen 5 6 2 Ala...

Page 3: ...n be powered through the USB connection The MyK is connected to the EIM through the modbus port RS485 which is wired to the KM5 connector on the EIM D is connected to KM5 2 D is connected to KM5 3 GND...

Page 4: ...he main screen The main screen shows the current superheat SH and opening degree OD in large characters If the main switch is off this will be shown with the characters OFF in large characters in the...

Page 5: ...essing escape will change the screen to the previous menu or function screen Main menu Login Parameters see Parameters Manual Control Readout Overview Service User2Factory Factory2User Service Info So...

Page 6: ...s 2 SOD Startup OD 0 100 0 2 OOD OD while OFF 0 100 0 2 RAL Reset alarm 0 1 0 0 OFF ON Regulation 0 SH Control 0 n09 Max superheat 2 0 20 0 16 0 K 0 n10 Min superheat 1 0 20 0 4 0 K 0 TSH Tn SH 10 18...

Page 7: ...14 R32 15 R227 16 R401A 17 R507 18 R402A 19 R404A 20 R407C 21 R407A 22 R407B 23 R410A 24 R170 25 R290 26 R600 27 R600a 28 R744 29 R1270 30 R417A 31 R422A 32 R413A 33 R422D 34 R427A 35 R438A 36 Opteon...

Page 8: ...ain makes it possible to toggle the manual control setting on or off by pressing the up or down buttons After setting the manual control mode to on press enter to accept the change It is now possible...

Page 9: ...s factory defaults This means that if a factory reset is performed these are the settings that will be used The Factory2User function will overwrite the current settings with settings that are stored...

Page 10: ...ed EIM The status of 8 different alarms are reported back from the EIM A 0 zero means that the alarm is not active a 1 means that the current alarm is active The active alarms screen displays details...

Reviews: