6

DKRCC.PS.RQ0.C2.02 / 520H8422                                      

© Danfoss A/S (AC-MCI/sw), 2014-03

6.5 Parameters

This is a list of the available parameters of the 

MyK application. The parameters in the Control, 

Regulation and Setup menus, are settings of the 

connected EIM. If no EIM is connected, “---” is 

displayed instead of the value. The MyK Setup 

and Password menus relate to the MyK applica-

tion itself. Please refer to the EIM manual for a 

description of the parameters concerning the 

setup of the EIM.

   

Group1

Group2

Parameter

Description

Min

Max

Default

Units

Level

Notes

Control

0

Reg Control

0

r12

Main switch

0

1

0

0

OFF;ON

o18

Manl control

0

1

0

1

OFF;MAN

o45

Manual OD %

0

100/480

0

%/step

1

Used when the o18 Manual 

Control is set to 1.

0%/0 step = fully closed,

100%/480 step = fully open.

% is chosen by default.

See “manual OD as steps” 

for changing to step.

tst

Startup time

0

1800

0

s

2

SOD

Startup OD

0

100

0

%

2

OOD

OD while OFF

0

100

0

%

2

RAL

Reset alarm

0

1

0

0

OFF;ON

Regulation

0

SH Control

0

n09

Max superheat

2.0

20.0

16.0

K

0

n10

Min superheat

1.0

20.0

4.0

K

0

TSH

Tn SH

10

1800

600

1

n22

SH close

0

16.0

0.5

K

1

SHL

SH Low

3.0

20.0

6.0

K

2

SHH

SH High

8.0

40.0

16.0

K

2

GaH

Gain High

0.5

50.0

1.0

2

GaL

Gain Low

0.1

50.0

12.5

2

TaH

Tau High

10

600

45

2

TaL

Tau Low

10

600

110

2

Aph

Alpha

15

600

130

1

n20

KpT0

-1.0

20.0

-1.0

2

CoS

Comp Speed

0.0

100.0

0.0

3

n09

Dyn max superheat

2.0

20.0

16.0

K

0

n10

Dyn min superheat

1.0

20.0

4.0

K

0

TSH

Dyn Tn SH

10

1800

600

1

Aph

Dyn Alpha

15

600

130

1

MOP

1

n11

MOP

0.0

200

13.7

bar

1

DMO

Diff MOP

-20.0

0.0

0.0

bar

2

KpM

Kp MOP

0.5

10.0

0.5

2

TnM

Tn Mop

30

600

180

2

Defrost

1

DeA

Def Activate

0

1

0

1

OFF;ON

DHO

Def Hold OD

0

100

30

%

2

DH1

Def Hold Ti 1

0

32000

120

s

2

DH2

Def Hold Ti 2

0

32000

60

s

2

DDO

Dyn def hold OD

0

100

30

%

3

Te Control

1

ter

Te Reference

-200.0

200.0

0.0

°C

1

KpT

Kp Te

0.5

10

1

2

TnT

Tn Te

30

600

60

2

External sensors

3

PEV

EvapPress P0

0

32000

0

bar

3

TS2

S2 temp

-200.0

200.0

0.0

°C

3

TS4

S4 Air temp

-200.0

200.0

0.0

°C

3

Summary of Contents for EIM 316

Page 1: ...e Features Configure EIM parameter Display setting Read out of status and parameters Manual control of the valve This application allows the user to configure the EIM316 336 parameters and display set...

Page 2: ...ion 4 2 References 4 3 Loading the application into the MyK 4 3 1 MyKManager 4 3 2 Copying 4 4 Connecting the MyK 4 5 Starting the application 5 6 Using the application 5 6 1 The main screen 5 6 2 Ala...

Page 3: ...n be powered through the USB connection The MyK is connected to the EIM through the modbus port RS485 which is wired to the KM5 connector on the EIM D is connected to KM5 2 D is connected to KM5 3 GND...

Page 4: ...he main screen The main screen shows the current superheat SH and opening degree OD in large characters If the main switch is off this will be shown with the characters OFF in large characters in the...

Page 5: ...essing escape will change the screen to the previous menu or function screen Main menu Login Parameters see Parameters Manual Control Readout Overview Service User2Factory Factory2User Service Info So...

Page 6: ...s 2 SOD Startup OD 0 100 0 2 OOD OD while OFF 0 100 0 2 RAL Reset alarm 0 1 0 0 OFF ON Regulation 0 SH Control 0 n09 Max superheat 2 0 20 0 16 0 K 0 n10 Min superheat 1 0 20 0 4 0 K 0 TSH Tn SH 10 18...

Page 7: ...14 R32 15 R227 16 R401A 17 R507 18 R402A 19 R404A 20 R407C 21 R407A 22 R407B 23 R410A 24 R170 25 R290 26 R600 27 R600a 28 R744 29 R1270 30 R417A 31 R422A 32 R413A 33 R422D 34 R427A 35 R438A 36 Opteon...

Page 8: ...ain makes it possible to toggle the manual control setting on or off by pressing the up or down buttons After setting the manual control mode to on press enter to accept the change It is now possible...

Page 9: ...s factory defaults This means that if a factory reset is performed these are the settings that will be used The Factory2User function will overwrite the current settings with settings that are stored...

Page 10: ...ed EIM The status of 8 different alarms are reported back from the EIM A 0 zero means that the alarm is not active a 1 means that the current alarm is active The active alarms screen displays details...