EIM 316/336 interface application for setup and configuration of MMIMyK

4

DKRCC.PS.RQ0.C2.02 / 520H8422                                      

© Danfoss A/S (AC-MCI/sw), 2014-03

5.  Starting the

 application 

The MyK will startup in its Bios menu if no 

application has previously been loaded. From 

this menu it is possible to load the applications 

that are stored on the MyK, either in its internal 

or external memory. Please refer also to the 

MMIMyK software download guide.

Select Application – Appl.Load, then select the 

disc that the application is stored on, 0:/ (internal 

memory) or 1:/ (SD/MMC card). Select the folder 

containing the application and press the enter 

button. The application should load automati-

cally and will startup after a few seconds. 

The next time the MyK is powered, it will start the 

application automatically. To enter the bios menu 

again, press the Esc and enter buttons at the same 

time, and keep them pressed for a few seconds, 

until the MyK enters the bios menu. From here it is 

possible to load another application.

6.  Using the

 application

6.1  The main screen

The main screen shows the current superheat (SH) 

and opening degree (OD) in large characters. 

If the main switch is off, this will be shown with 

the characters OFF in large characters in the 

upper right corner. If the main switch is on, the 

currently active superheat reference is shown in 

the upper right corner instead.

If an alarm is present, this is indicated by the 

word “ALARM” to the right of the opening 

degree. If the unit is in manual control mode, this 

is indicated with the word “MAN”. 

Pressing enter will give access to the main menu. 

Pressing escape will give access to the alarm screen. 

If the MyK does not recognize that it is con-

nected to an EIM 336, it will beep to indicate 

that it is in alarm. 

On the main screen press enter and go to 

“Parameters-> MyK setup-> System”.

Under “Active EIM Addr”, set the correct ID of 

the EIM 336 you want to connect to. Under 

“Serial baud rate (MB)” set the baud rate to the 

Setting up the MYK to  

specific EIM 336 unit 

address.

correct baud rate (default for EIM is 192 i.e. 19200 

Baud) then after set the correct serial settings 

under “Serial settings (MB)”, (default value for EIM 

336 is 8E1 i.e. 8 data bits, even parity and 1 stop 

bit). The MyK should now able to connect with 

the EIM 336. 

Summary of Contents for EIM 316

Page 1: ...e Features Configure EIM parameter Display setting Read out of status and parameters Manual control of the valve This application allows the user to configure the EIM316 336 parameters and display set...

Page 2: ...ion 4 2 References 4 3 Loading the application into the MyK 4 3 1 MyKManager 4 3 2 Copying 4 4 Connecting the MyK 4 5 Starting the application 5 6 Using the application 5 6 1 The main screen 5 6 2 Ala...

Page 3: ...n be powered through the USB connection The MyK is connected to the EIM through the modbus port RS485 which is wired to the KM5 connector on the EIM D is connected to KM5 2 D is connected to KM5 3 GND...

Page 4: ...he main screen The main screen shows the current superheat SH and opening degree OD in large characters If the main switch is off this will be shown with the characters OFF in large characters in the...

Page 5: ...essing escape will change the screen to the previous menu or function screen Main menu Login Parameters see Parameters Manual Control Readout Overview Service User2Factory Factory2User Service Info So...

Page 6: ...s 2 SOD Startup OD 0 100 0 2 OOD OD while OFF 0 100 0 2 RAL Reset alarm 0 1 0 0 OFF ON Regulation 0 SH Control 0 n09 Max superheat 2 0 20 0 16 0 K 0 n10 Min superheat 1 0 20 0 4 0 K 0 TSH Tn SH 10 18...

Page 7: ...14 R32 15 R227 16 R401A 17 R507 18 R402A 19 R404A 20 R407C 21 R407A 22 R407B 23 R410A 24 R170 25 R290 26 R600 27 R600a 28 R744 29 R1270 30 R417A 31 R422A 32 R413A 33 R422D 34 R427A 35 R438A 36 Opteon...

Page 8: ...ain makes it possible to toggle the manual control setting on or off by pressing the up or down buttons After setting the manual control mode to on press enter to accept the change It is now possible...

Page 9: ...s factory defaults This means that if a factory reset is performed these are the settings that will be used The Factory2User function will overwrite the current settings with settings that are stored...

Page 10: ...ed EIM The status of 8 different alarms are reported back from the EIM A 0 zero means that the alarm is not active a 1 means that the current alarm is active The active alarms screen displays details...

Reviews: