32d
Service parameter(s) 21-22
21 Total stop
Setting range
Factory setting
ON / OFF
OFF
Decide whether you want a total stop during the setback
temperature period.
ON:
The desired system temperature is lowered
to 10 °C. The min. setting of the temperature
(line 2, section 22) is overruled.
Desired system
temp. (°C)
10 °C
Time
OFF:
No total stop
Desired system
temp. (°C)
10 °C
Time
22 Pump exercise
Setting range
Factory setting
ON / OFF
ON
Exercises the pump to avoid blocking in periods without heat
demand.
ON:
The pump is switched ON for 1 minute every
third day around noon.
OFF:
The pump exercise is not active.