Service parameter(s) 174-197
32j
174 Motor protection
Setting range
Factory setting
OFF / 10 ... 59 min.
OFF
Prevents the controller from unstable temperature control (and
resulting actuator oscillations). This can occur when there is
no DHW tapping, i.e. when the load is only due to the DHW
circulation, or when the heating demand in the heating circuit
is very low. The motor protection increases the lifetime of all
involved components.
OFF:
Motor protection is not activated.
10 ... 59:
Motor protection is activated after the set
activation delay.
A high value should be used for DHW
installations with many consumers.
189 Min. activation time, gear motor
Setting range
Factory setting
2 ... 10
6
The min. pulse length in milliseconds for activation of the gear
motor.
Setting
Pulse length
2
40 ms
3
60 ms
6
120 ms
10
200 ms
The setting should be corrected if the gear motor is too sensitive
to short activation pulses.
196 Service pin - LON
Setting range
Factory setting
ON / OFF
OFF
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).
197 LON reset
Setting range
Factory setting
ON / OFF
ON
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).