Con
tr
ol & o
ver
vie
w
s
ECL Comfort settings
30
A
Time and date
Section 17
B
System information
Sections 18 & 19
C
Heat curve
Section 20
Setting ranges
Factory settings
Your settings
Slope
0.2 ... 3.4
1.8
See section 20
Parallel displacement
-15 ... 20
0 K
See section 20
1
Limit for heating cut-out
10 ... 30 °C
18 °C
See section 21
2
Flow temperature , min. / max. limits
10 ... 110 °C
min. 10, max. 90 °C
See section 22
3
Room temperature influence
0 ... 99 / -99 ... 0
min. 0, max. -40
See section 23
4
Proportional band, Xp
1 ... 250 K
80 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec.
30 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec.
35 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K
3 K
See section 26
Summary of Contents for ECL Comfort P30
Page 4: ......