Service parameter(s) 15-20
32c
15 Adaptive function of room temperature
Setting range
Factory setting
OFF / 1 ... 30
OFF
Controls how fast the room temperature adapts to the desired
room temperature.
The adaptive funtion will eliminate the difference
between the desired and the actual room
temperature. This is done by integrating the
difference and adjusting the desired flow
temperature.
OFF:
The adaptive funtion is cancelled.
1:
The desired temperature is adapted quickly.
30:
The desired temperature is adapted slowly.
20 Optimization based on room / outdoor temperature
Setting range
Factory setting
ON / OFF
OFF
The optimized start and stop time can be based on either room or
outdoor temperature.
ON:
Optimization based on room temperature, if
measured.
OFF:
Optimization based on outdoor
temperature. Use this setting if the room
temperature is not measured.