6.8.8 Sensor offset (new functionality as from firmware 1.59)
The measured temperature can be offset adjusted in order to
compensate for cable resistance or a not-optimum place for the
temperature sensor. The adjusted temperature can be seen in "Raw
input overview" and "Input overview".
Common controller > System > Sensor offset
Sensor 1 . . . (temperature sensor)
Circuit
Setting range
Factory setting
*
*
Setting the offset of the measured temperature.
Positive
offset
value:
The temperature value is increased
Negative
offset
value:
The temperature value is decreased
6.8.9 Display
Backlight (display brightness)
60058
Circuit
Setting range
Factory setting
0 ... 10
5
Adjust the brightness of the display.
0:
Weak backlight.
10:
Strong backlight.
Contrast (display contrast)
60059
Circuit
Setting range
Factory setting
0 ... 10
3
Adjust the contrast of the display.
0:
Low contrast.
10:
High contrast.
6.8.10 Communication
Modbus addr.
38
Circuit
Setting range
Factory setting
1 ... 247
1
Set the Modbus address if the controller is part of a Modbus
network.
1 ... 247:
Assign the Modbus address within the stated setting
range.
VI.GU.L2.02
© Danfoss | 2017.09 | 169