A375.1, example d
2 x boiler ON / OFF control for a heating circuit. The boiler circuit is equipped with a low loss header.
* = pressure relief valve
The pumps in the boiler are not controlled.
Rotating sequence: Burner 1 is active before burner 2. Next day burner 2 is active before burner 1.
One burner step is active at low heat demand. At increased heat demand the next burner step is activated additionally
The last burner step can be disabled if the outdoor temperature is higher than a set value.
Special settings for type A375.1, example d:
Navigation:
ID no.:
Recommended setting:
Heating circuit (circuit 1)
Sequence type (code) for controlling the burners:
MENU \ Settings \ Boiler: 'Sequence type'
11072
0
Number of total burner steps:
MENU \ Settings \ Boiler: ‘Steps'
11073
2
VI.GU.L2.02
© Danfoss | 2017.09 | 35
Operating Guide ECL Comfort 210/296/310, application A275/A375