5.10 Alarm
Alarm for monitoring the flow temperature is only available in
circuit 2 in A275.3 and A375.3 applications.
Many applications in the ECL Comfort 210 and 310 series have an
alarm function. The alarm function typically activates relay 4 (ECL
Comfort 210) or relay 6 (ECL Comfort 310).
The alarm relay can activate a lamp, a horn, an input to an alarm
transmitting device etc.
The relay in question is activated as long as the alarm condition
is present.
Typical alarms:
•
Actual flow temperature differs from the desired flow
temperature.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
5.10.1 S9 pressure
MENU > Settings > Alarm
Low X
1x607
Definition of which voltage value corresponds to which position value.
The voltage (as a 0 - 10 volt signal) comes from a position measuring in
M1 and is applied to input S11 (ECA 32). This input voltage is converted to
display a % value for the position of M1.
See also "Position" and "High X".
See Appendix “Parameter ID overview”
X
= Volt
Y
= Position
# 1 # = Low X