MENU > Common controller > System > M-bus config.
Scan time
Energy meter 1 (2, 3, 4, 5)
6002
Circuit
Setting range
Factory setting
-
1 - 3600 sec
60 sec
Setting the scanning time for acquiring data of connected energy
meter(s).
If the energy meter is battery powered, the scan time should be set to
a high value to prevent a too fast battery draining.
Oppositely, if the flow / power limitation function is used in the ECL
Comfort 310, the scan time should be set to a low value in order to
have quick limitation.
MENU > Common controller > System > M-bus config.
ID
Energy meter 1 (2, 3, 4, 5)
Read-out
Circuit
Setting range
Factory setting
-
-
-
Information about the energy meter's serial no.
MENU > Common controller > System > Energy meters
Energy meter 1 (2, 3, 4, 5)
Read-out
Circuit
Setting range
Factory setting
-
0 - 4
0
Information from actual energy meter about, for example, ID,
temperatures, flow / volume, power / energy.
The shown information depends on the settings made in the “M-bus
config.” menu.
6.8.7 Raw input overview
Measured temperatures, input status and voltages are displayed.
In addition, a detection of malfunctions can be chosen for activated
temperature inputs.
Monitoring the sensors:
Choose the sensor which measures a temperature, for example the
S5. When the dial is pressed, a magnifying glass
appears in the
selected line. The S5 temperature is now being monitored.
Alarm indication:
Should the connection to the temperature sensor be disconnected,
short-circuited or the sensor itself be defective, the alarm function
is activated.
In the "Raw input overview" an alarm symbol
is shown at the
defective temperature sensor in question.
Resetting the alarm:
Choose the sensor (S number) for which you want to clear the
alarm. Press the dial. The magnifying glass
and alarm symbols
disappear.
When the dial is pressed again, the monitoring function is
reactivated.
The temperature sensor inputs have a measuring range from -60 ...
150 ° C.
If a temperature sensor or its connection breaks, the value indication
is " - - ".
If a temperature sensor or its connection is short-circuited, the value
indication is " - - - ".