VMBNB72J

Ÿ

  Pipe installation must be carried out by an authorized installer . 

The installation must be carried out according to the appli-

cable building regulations .

Ÿ

  Cold and hot water lines and overflow lines from safety valves 

must be made of heat resistant and anti-corrosive material, 

e .g . copper . The safety valve’s overflow lines must have an 

open connection with the outlet and be visible in a frost free 

environment .

 

 

NOTE! The tank must be connected to an expansion tank 

and safety valve in such a way that the connection cannot 

be shut off .

1.5 

Temperature

Ÿ

  Highest permitted temperature on DWH primary side is 100°C . 

On the secondary side the temperature is limited to 90-95°C 

due to the factory installed safety valve for temperature and 

pressure .

Maintenance

2.1 

Water temperature

Ÿ

  According to the building regulations, output hot water tem-

perature must not exceed 65°C . At higher tank temperatures 

the mixing valve can be installed to limit the output hot water 

temperature .

Ÿ

  Output temperature should be kept as low as possible, alt-

hough +45°C at the lowest at the tap .

Ÿ

  The lower the temperature in the system the lower the heat 

losses from the pipes and valves .

2.2 

Safety valve

The safety valve is protection against the over pressure in the 

closed hot water tank and must therefore be regularly inspected .

Ÿ

  The safety valve can be checked by turning the cap until the 

valve lets out some water through the overflow pipe . This 

must be carried out at least four times a year .

Ÿ

  If a safety valve does not work properly, it must be replaced . 

CONTACT AN AUTHORISED TECHNICIAN!

Ÿ

  If the safety valve is not checked regularly, the hot water tank 

might be damaged . 

Ÿ

  It is quite normal for the safety valve to let out small amounts 

of water when the hot water tank is being charged, especially 

if a lot of hot water was used previously . The opening pressure 

of the safety valves is not adjustable .

Ÿ

  The safety valve is mounted on the cold water inlet line, hori-

zontally with its outlet opening facing downwards . 

2.3 

Water quality

The indirect heating of the water for consumption is an advan-

tage, which makes Danfoss DWH suitable in areas with high cal-

cium levels in the water . In installations where the water comes 

from a well the water should be checked to ensure that it cannot 

cause damage to the hot water installation .

Ÿ

  Stainless steel tanks and pipes should not be exposed to water 

with high chloride levels .

 

 

With very poor water quality, a water filter must be instal-

led in the installation . A water analysis will provide indica-
tion of any necessary remedial actions .

2.4 

Sensors

When DWH is installed in conjunction with DHP-L connect the 

sensors in the water heater to the following connections:

Ÿ

  Sensor hot-water – 311-312

Ÿ

  Sensor hot-water top – 325-3262 .4  Minimum headroom

2.5 

Minimum headroom

1905 

 

1620 

 

DWH 300

DWH 200

Figure 3: Minimum headroom .

2.6 

Installation carried out by:

PIPE INSTALLATION 

Date   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Company   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Name  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Tel . No .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

ELECTRICAL INSTALLATION

Date   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Company   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Name  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Tel . No .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

If these instructions are not followed during installation, ope-

ration and maintenance, Danfoss AS’s liability according to the 

applicable warranty is not binding .
Danfoss AS retains the right to make changes to components 

and specifications without prior notice .

Summary of Contents for DWH 200

Page 1: ...appendix 4 DE Installation Wartung 11 DA Installation Vedligeholdelse 13 NL Installatie Onderhoud 15 FR Installation Maintenance 17 ES instalaci n Mantenimiento 19 PL Instalacja Konserwacja 21 CS Inst...

Page 2: ...d by another heat source any energy forms can therefore be used with it The hot water tank is designed according to Pressure equipment 97 23 EC article 3 3 1 2 Connections and dimensions 455 596 690 4...

Page 3: ...properly it must be replaced CONTACT AN AUTHORISED TECHNICIAN If the safety valve is not checked regularly the hot water tank might be damaged It is quite normal for the safety valve to let out small...

Page 4: ...essential part of the product It should be kept with the appliance so that it can be consulted by the user and our authorised personnel Please read carefully the instructions and notices about the ap...

Page 5: ...5 VMBNB72J Manufacturer labels 1 1 The water heaters are marked with durable permanently fixed labels Manufacturer labels 1 1 1...

Page 6: ...discharge pipe switch the heater off and contact the installer WARNING TO THE INSTALLER a This installation is subject to building regulation approval notify the Local Authority of intention to instal...

Page 7: ...Danfoss code reference UNV0300 Package contents Position Danfoss code Number Description 2 FITT0051 1 Expansion vessel 19 Litre FITT0052 1 Expansion vessel bracket 3 FITT0053 1 Flexible hose FITT0001...

Page 8: ...sion Vessel 3 Flexible hose 5 Unvented manifold assembly Pressure Reducing Valve Safety Relief Valve Non return Valve 6 Shut off Valve 7 Double Check Valve with Shut off Valve 8 Flexible hose 9 Safety...

Page 9: ...tal discharge pipe from tundish with continuous fall 5 Discharge below fixed grating 6 Trapped gully Sizing of copper discharge pipe 4 for common temperature relief valve outlet sizes Valve outlet siz...

Page 10: ...system follow the instructions below 1 Close the shut off valve on the incoming water supply 2 Open both cold and hot water taps which are situated as low as possible in the building to depressu rise...

Page 11: ...ere W rmequelle vorgenommen wird daher k nnen beliebige Energiearten genutzt werden Der Warmwasserbereiter ist gem der Druckger terichtlinie 97 23 EG Absatz 3 3 konstruiert 1 2 Anschl sse und Abmessun...

Page 12: ...entil nicht einwandfrei funktionieren muss es ausgetauscht werden WENDEN SIE SICH AN EINEN ZUGELASSENEN TECHNIKER Wird das Sicherheitsventil nicht regelm ig gepr ft besteht die Gefahr von Sch den am W...

Page 13: ...nden varmekilde den kan derfor bruges til alle energikilder Varmtvandsbeholderen er konstrueret iht direktivet vedr rende trykb rende udstyr 97 23 EC artikel 3 3 1 2 Tilslutning og m l 455 596 690 40...

Page 14: ...orrekt skal den skiftes KONTAKT EN AUTORISERET TEKNIKER Hvis sikkerhedsventilen ikke efterses j vnligt er der risiko for skader p varmtvandsbeholderen Det er helt normalt at sikkerhedsventilen lukker...

Page 15: ...er door een andere warmtebron wordt geproduceerd daardoor kan iedere vorm van energie hiervoor worden gebruikt De boiler is ontworpen volgens drukapparatuur 97 23 EG artikel 3 3 1 2 Aansluitingen en a...

Page 16: ...de veiligheidsklep niet regelmatig wordt gecontroleerd kan de boiler beschadigd raken Het is volkomen normaal dat er kleine hoeveelheden water uit de veiligheidsklep druppelen wanneer de boiler volloo...

Page 17: ...avec toutes les formes d nergie Le r servoir est conforme la norme applicable aux quipe ments sous pression 97 23 EC article 3 3 1 2 Connexions et dimensions 455 596 690 40 10 1 2 3 4 5 6 7 H Figure...

Page 18: ...upape de s curit tourner le bouchon jusqu ce qu un peu d eau s coule du trop plein R p ter cette op ration au moins quatre fois par an Remplacer la soupape de s curit lorsqu elle ne fonctionne plus co...

Page 19: ...imentaci n 22 mm 5 Entrada de cable el ctrico 6 Ventilaci n calentador de agua inoxidable 7 V lvula de seguridad Danfoss DWH 200 300 Volumen Sec Princ l 180 7 5 286 10 Presi n dise o Sec Princ MPa 1 0...

Page 20: ...ISE A UN T CNICO AUTORIZADO Si la v lvula de seguridad no se comprueba peri dicamente el dep sito de agua caliente podr a da arse Es bastante normal que la v lvula de seguridad deje salir peque as can...

Page 21: ...i zku z czym mo na z nim stosowa dowolne formy energii Zasobnik c w u jest zaprojektowany zgodnie z wymogami dyrek tywy 97 23 WE Artyku 3 3 w sprawie urz dze ci nieniowych 1 2 Wymiary i przy cza 455 5...

Page 22: ...d owo nale y go wymieni SKONTAKTUJ SI Z WYKWALIFIKOWANYM INSTALATOREM Je li zaw r bezpiecze stwa nie b dzie regularnie sprawdzany zasobnik c w u mo e ulec uszkodzeniu To normalne e zaw r bezpiecze stw...

Page 23: ...ojem tepla proto ji lze pou t s jak mikoliv typy energie N dr na teplou vodu je navr ena podle sm rnice pro tlakov za zen 97 23 ES l nku 3 3 1 2 P pojky a rozm ry 455 596 690 40 10 1 2 3 4 5 6 7 H Obr...

Page 24: ...nefunguje spr vn mus se vym nit OBRA TE SE NA AUTORIZOVAN HO TECHNIKA Pokud se pojistn ventil pravideln nekontroluje m e doj t k po kozen n dr e na teplou vodu Je pln norm ln e p i pln n n dr e na te...

Page 25: ...toru 22 mm 2 Kuum vesi 22 mm 3 K lm vesi 22 mm 4 Toitetoru 22 mm 5 Elektrijuhe sisse 6 Ventilatsioon roostevabast terasest boiler 7 Kaitseklapp Danfoss DWH 200 300 Maht sek prim l 180 7 5 286 10 Kavan...

Page 26: ...DUST KVALIFITSEERITUD TEHNIKUGA Kui kaitseklappi ei kontrollita regulaarselt v ib veepaak kah justuda Veepaagi laadimise ajal kaitseklapist v heses koguses v ljuv vesi on t iesti normaalne n htus erit...

Page 27: ...VMBNB72J...

Page 28: ...VMBNB72J...

Reviews: