Low Pressure Limiter

Scale plate directly indicates Low Switching Point. There is no 
pointer for Differential.
Differential value is fixed and printed on the scale plate.
1.  Set Low Switching Point by adjusting range screw (fig. 7)
2.  High Switching Point is equal to Low Switching Point plus 
  Differential:

HIGH = LOW + DIFFERENTIAL

High Pressure Limiter

Scale plate directly indicates High Switching Point. There is no 
pointer for Differential.
Differential value is fixed and printed on the scale plate.
1.  Set High Switching Point by adjusting range screw (fig. 7)
2.  Low Switching Point is equal to High Switching Point less 
  Differential:

LOW = HIGH - DIFFERENTIAL

Protection for settings

The protective cap on adjustment screws may be used to lock and 
seal the settings (fig. 6)

Manual reset

For resetting use the screwdriver (Fig. 5)
Manual reset is possible to operate only after return of pressure to 
cut-in level.
Before releasing the reset, the cause of the shutdown must be 
found and eliminated.

BCP pressure controller with auto reset as a 
limiting device

Since the pressure controller BCP has no lockout with manual 
resetting, this function must be realized externally as a part of a 
safety logic e.g. by external contactors and/or relays which then 
are to be used according to the requirements of prEN50156-1 
standard for safety relevant hardware.

External closure must not be interlocked, while loss of auxiliary 
energy must lead to a closure.
Resetting must not be automated; it has to be performed 
manually.
Resetting on fault must lead to a repeated closure. When BCP 
limits, for rising or falling application, the external safety logic 
must change to the fail safe position. 

Endurance of any external contactors and relays must be accord-
ing to EN12952-11, which means 250000 switching cycles under 
conditions similar to operating conditions and be capable of a 
mechanical life time of 3000000 switching cycles. 
Conditions similar to operating conditions include chemical and 
climatic influences as well as electrical and mechanical stresses. 
In addition, contactors must fulfil EN60947 and relays must fulfil 
EN60255.

BCP with double bellows

BCP6, BCP6H, BCP7, and BCP7H have a double bellows; an outer 
bellows and a regulating (inner) bellows.
When system pressure exceeds the set value, the BCP will 
automatically stop the plant. The double bellows system prevents 
loss of media in the event of bellows rupture. A rupture in the 
inner bellows will cause the control cut-out pressure to fall about 
3 times less the set value, thus the system will stop. A rupture in 
the outer bellows will cause the control cut-out pressure to fall to 
about 3 bar under the set value, thus providing a fail-safe function.

                                    

 

Safety requirements

Installation

t *OUFSOBMSVMFTBOEMFHJTMBUJPODVSSFOUJOUIFDPVOUSZDPODFSOFE

  with respect to health and safety at work must be observed

t 'PSTBGFUZSFBTPOTUIFJOTUBMMBUJPOPGQSFTTVSFDPOUSPMTNVTUCF

  carried out only by qualified staff, trained in all technical aspects  
  of their operation

t #FGPSFJOTUBMMBUJPOUIFQJQFTNVTUCFEFQSFTTVSJTFEBOEQVSHFE

  (empty of its fluid) in order to avoid any danger to the operator

t *UJTFTTFOUJBMUPJTPMBUFUIFQPXFSTVQQMZCFGPSFXJSJOH

  connections are made to avoid possible electrical shock or 
  damage to equipment. Never touch live parts with your fingers  
  or with any tool

t %*/QMVHTVQQMJFECZ%BOGPTTBOEDBCMFBQQSPWFEGPSUIF

  application must be used. The cable must be connected with  
  adequate stress relief in order to prevent that pullig forces can  
  be carried through the cable to the plug

Commissioning

Before putting pressure control into operation, check that:

t 5IFXPSLJOHDPOEJUJPOTBSFDPNQBUJCMFXJUIUIFEFUBJMTHJWFOJO

  the product label and this instruction notice

t "MMFMFDUSJDBMDPOOFDUJPOTIBWFCFFOQSPQFSMZNBEF
t *OTUBMMBUJPOJTUJHIUBGUFSBTTFNCMZ

Operation

t 5IJTOPUJDFNVTUCFBWBJMBCMFPOTJUFXIFSFQSFTTVSFDPOUSPMT

  are installed

t *OUFSOBMSVMFTBOEMFHJTMBUJPODVSSFOUJOUIFDPVOUSZDPODFSOFE

  with respect to health and safety at work must be observed

t 1FSTPOOFMDBSSZJOHPVUBOZJOUFSWFOUJPOPOUIFQSFTTVSFDPOUSPM

  must be qualified for the task

t 5IFQSFTTVSFDPOUSPMTIPVMECFDIFDLFESFHVMBSMZUPTFFJGJU

  operates properly

t 5IF#$1DPWFSNVTUOPUCFSFNPWFEVOEFSBOZDJSDVNTUBODFT
t "OZPWFSMPBEPGUIFQSFTTVSFDPOUSPMNVTUCFQSFWFOUFE

  Overloaded or damaged control must be exchanged

t *UJTFTTFOUJBMUPEJTDPOOFDUUIFQMVHCFGPSFEJTNPVOUJOHUIF

  control from the system

t "MMPQFSBUJPOTNVTUCFQFSGPSNFEVTJOHTVJUBCMFUPPMT
t *UJTUIFSFTQPOTJCJMJUZPGUIFVTFSUPDIFDLUIBUUIFSFJTOP

  leakage after a faulty operation or on a periodic basis under  
  normal conditions

t 0OMZQSFTTVSFDPOUSPMTEFTJHOFEDPOTUSVDUFEBOESFMFBTFE

  by Danfoss must be used for the applicaiton concerned. 
  Danfoss can accept no responsibility in case of alterations made  
  on the pressure controls or the use of them against the 
  instructions of Danfoss

t %BOGPTTJTOPUSFTQPOTJCMFGPSBOZEBNBHFXIJDINBZCF

  caused by the use of parts, accessories or controls which are not  
  original Danfoss parts

          

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

        

Instructions

Summary of Contents for BCP1

Page 1: ...4 Rys 5 Rys 6 Rys 7 Rys 8 017R9328 017R9328 Danfoss A S 03 2009 RA MC mr IC PI P10 K4 49 520B3567 1 Instrukcja Akcesoria do monta u uchwyt na cienny monta na szynie DIN Mounting accessories Accessoire...

Page 2: ...eczyszczenia rury przy czeniowej konieczny jest monta kt ry umo liwi p niejsze wyczyszczenie uk adu Rurka przy czeniowa i po czenie z kot em musi zosta tak zaprojektowane aby umo liwi wyczyszczenie i...

Page 3: ...ma aplikacj Konstrukcja dwu mieszkowa zabezpiecza aplikacj przed utrat medium w momencie p kni cia jednego z mieszk w P kni cie mieszka wewn trznego spowoduje trzykrotny spadek warto ci ci nienia odci...

Page 4: ...ipe Such purging must not remove the water seal or introduce dirt into the water seal In addidition the connection pipe and its boiler connection must be designed for cleaning and inspection and have...

Page 5: ...in the inner bellows will cause the control cut out pressure to fall about 3 times less the set value thus the system will stop A rupture in the outer bellows will cause the control cut out pressure t...

Page 6: ...werden Zus tzlich muss das Anschlussrohr und seine Kesselverbindung zur Reinigung und Kontrolle ausgelegt sein und eine freie Boh rung der folgenden Mindestgr e haben 1 Wenn das Rohr nur den Druckbeg...

Page 7: ...n eingestellten Wert berschreitet schaltet das Ger t automatisch die Anlage aus Das doppelte Wellrohrsystem verhindert Medienverlust bei einem Bruch des Wellrohrs Bei Bruch des inneren Wellrohrs schal...

Page 8: ...n raccord au g n rateur doivent tre accessibles au nettoyage et l inspection et pr senter un al sage net d au moins 1 Pour un tuyau alimentant uniquement le limiteur 8mm si le tuyau mesure moins d 1m...

Page 9: ...t l installation Le syst me double souf flet vite la perte de fluide en cas de rupture d un soufflet En cas de rupture du soufflet int rieur la pression d ouverture du r gu lateur chute environ 3 fois...

Page 10: ...m si el tubo mide menos de 1 m de largo 15 mm si el tubo mide m s de 1 m de largo 2 Si el tubo suministra a m s de un limitador 20 mm para todos los tipos de tubo Prueba de funcionamiento del limitado...

Page 11: ...Si se produjera la ruptura del fuelle el sistema de doble fuelle evitar a que se perdieran los medios La ruptura del fuelle interior provo car una disminuci n de la presi n de desconexi n del contro l...

Page 12: ...do e il relativo raccordo per caldaia devono essere progettati tenendo a mente le operazioni di pulizia e di con trollo e devono avere un alesaggio ben definito di almeno 1 Se il tubo alimenta solo il...

Page 13: ...to esterno e un soffieto di regolazione interno Quando la pressione del sisterna supera il valore impostato il BCP arresta automaticamente l impianto Il sistema con doppio soffi etto evita perdite di...

Reviews: