safety Notes

Prior to assembly and commissioning 

to avoid injury of persons and damages 

of the devices, it is absolutely necessary 

to carefully read and observe these 

instructions.

Necessary assembly, start-up, and 

maintenance work must be performed 

only by qualified, trained and authorized 

personnel. 

Prior to assembly and maintenance work 

on the controller, the system must be:

-  depressurized, 

-  cooled down,

-  emptied and 

-  cleaned.

Please comply with the instructions of the 

system manufacturer or system operator.

Definition of Application

The controller is used for pressure relief  

control of water and water glycol mixtures 

for heating, district heating and cooling 

systems. 

The technical parameters on the product 

labels determine the use.

Assembly

Admissible Installation Positions 

Medium temperatures up to 100 °C 

:

-  Can by installed in any position.

Medium temperatures > 100 °C 

:

-  Installation permitted only in 

horizontal pipelines with the 

actuator oriented downwards.

Installation location and 

Installation scheme 

AVP (-F) return mounting 

AVP (-F) flow mounting 

Valve Installation

 

1.   Clean pipeline system prior to assembly.
2.  The installation of a strainer in 

front of the controller is strongly 

recommended 

.

3.  Install pressure indicators in front of and 

behind the system part to be controlled.

4.  Install valve

•  The flow direction indicated on 

the product label 

 or on the 

valve 

 must be observed.

•  The valve with mounted weld-

on tailpieces may only be 

spotwelded to the pipeline 

.

  The weld-on tailpieces may be welded 

only without the valve and seals! 

  If these instructions are not observed, 

high welding temperatures 

may destroy the  seals.

•  Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces 

must be clean and without any 

damage. 

Tighten screws in flanges 

crosswise in 3 steps up to the 

maximum torque (50 Nm).

5. 

Caution

:  

Mechanical loads of the valve body by the 

pipelines are not permitted

 

.

Impulse tube and seal pot mounting

•  Which impulse tubes to use?

 

  Use Impulse tube set AV 

 or 

use following pipe: 

Copper Ø 6 × 1 mm EN 12449 

•  Connection of impulse tube and seal pot 

 in the system

 

-  Return mounting 

-  Flow mounting 

•  Connection to the pipeline 

  It is strongly recommended to install the 

impulse tube to the pipeline horizontally 

 or upwards 

  This prevents dirt accumulation in the 

impulse tube and possible malfunction 

of the controller.

  Connection downwards is not 

recommendable 

.

•  Impulse Tube Mounting 

1. Cut pipe perpendicularly to the pipe 

axis and smooth edges out 

.

2. Press impulse tube 

 into the 

threaded joint up to its stop.

3. Tighten union nut 

 Torque 14 Nm

Insulation 

For medium temperatures up to 100 °C the 

pressure actuator 

 may also be insulated.

Dimensions, Weights

 

(See page 2)

1)

   Conical ext. thread acc. to EN 10226-1

2)

   Flanges PN 25, acc. to EN 1092-2

Other flange dimensions - see table for 

tailpieces.

start-up

 

Filling the system, first start-up

1.  Slowly open shut-off devices 

 in the 

flow pipeline.

2.  Slowly open shut-off devices 

 in the 

return pipeline.

3.  Slowly open shut-off devices 

 in the 

flow pipeline.

4.  Slowly open shut-off devices 

 in the 

return pipeline.

leak and Pressure Tests

Pressure must be gradually increased at 

the +/- connection 

.

Non-compliance may cause  damages at 

the actuator or the valve.

A pressure test of the entire system 

must be carried out in accordance with 

manufacturer’s instructions.

The maximum test pressure is: 

1.5 × PN

PN - see product label!

Putting out of operation

1.  Slowly close shut-off devices 

 in the 

flow pipeline.

2.  Slowly close shut-off devices 

 in the 

return pipeline.

settings

Differential Pressure setting 

(not relevant at fixed setting version AVP-F)

The pressure setting range is indicated on 

the product label 

.

Procedure:

1.  Start system, see section “Filling the 

system, first start-up“  

Completely open all shut-off devices in 

the system.

2.  Set flow rate on a motorised valve 

, on 

which differential pressure is controlled, 

to about 50 %.

3.  Adjustment

  Observe pressure indicators 

 or/and  

alternatively see handle scale indication.

  Turning to the right    (clockwise) 

 

increases the set-point (stressing the 

spring). 

Turning to the left (counter clockwise) 

 reduces the set-point (releasing the 

spring).

If the required differential pressure is not 

attained, a cause may be a too small 

pressure loss in the system.

seal

 

The set-point adjuster can be sealed by a 

seal wire 

, if necessary.

ENglIsh

Summary of Contents for AVP Series

Page 1: ... AVP AVP F www danfoss pl Strona 11 РУССКИЙ Регулятор перепада давлений AVP AVP F www danfoss ru Стр 12 Lietuvių k Slėgio perkryčio reguliatorius AVP AVP F www danfoss com Puslapis 13 NEDERLANDS Differential pressure controller AVP AVP F www danfoss nl Blz 14 MAGYAR Nyomáskülönbség szabályozó AVP AVP F www danfoss hu 15 oldal Română Regulator de presiune diferenţială AVP AVP F www incalzire danfos...

Page 2: ...184 204 234 k 65 75 85 100 110 125 d2 14 14 14 18 18 18 n 4 4 4 4 4 4 AVP PN16 DN 15 20 25 32 flow return flow return flow return flow return L mm 65 70 75 100 H 232 232 232 232 H2 34 34 37 38 AVP F PN16 DN 15 20 25 32 flow return flow return flow return flow return L mm 65 65 70 75 100 H 97 97 97 97 97 H2 34 34 34 37 38 AVP PN25 DN 15 20 25 32 40 50 flow return flow return flow return flow return...

Page 3: ... R 1 8 R3 8 R 1 2 EN 10226 DN L mm 15 69 20 74 25 79 32 104 40 114 50 134 73695010 DH SMT SI VI DB N3 8I Danfoss 04 2009 3 ...

Page 4: ... 100 C 73695010 DH SMT SI VI DB N3 8I Danfoss 04 2009 4 Δp 1 0 4 5 bar 100 C ...

Page 5: ...2449 Connection of impulse tube and seal pot in the system Return mounting Flow mounting Connection to the pipeline It is strongly recommended to install the impulse tube to the pipeline horizontally or upwards This prevents dirt accumulation in the impulse tube and possible malfunction of the controller Connection downwards is not recommendable Impulse Tube Mounting 1 Cut pipe perpendicularly to ...

Page 6: ...stemet Montering i returledning Montering i flowledning Tilslutning til rørledning Det anbefales stærkt at montere impulsledningen vandret eller opad på rørledningen Dette forhindrer snavsophobning i impulsledningen samt evt forringelse af regulatorfunktionen Det kan ikke anbefales at montere impulsledningen nedad Montering af impulsledning 1 Skær røret over vinkelret på rørets akse og afglat ende...

Page 7: ...luss der Steuerleitung in der Anlage Einbau im Rücklauf Einbau im Vorlauf Anschluss an der Rohrleitung Die Steuerleitung waagerecht oder nach oben an die Rohrleitung anschließen Dies verhindert Verschmutzung der Steuerleitung und mögliche Störungen des Reglers Anschluss nicht nach unten Montage Steuerleitung 1 Rohr rechtwinklig ablängen und entgraten 2 Steuerleitung in die Verschraubung bis zum An...

Page 8: ...de impulsión en el sistema Montaje en retorno Montaje en impulsión Conexión a la tubería Se recomienda instalar el tubo de impulsión horizontalmente a la tubería o hacia arriba Esto previene la acumulación de suciedad en el tubo de impulsión y el posible mal funcionamiento del controlador No es recomendable instalarlo hacia abajo Montaje del tubo de impulsión 1 Corte el tubo perpendicularmente al ...

Page 9: ...njo vrsto cevi bakrena Ø 6 1 mm EN 12449 Priključitev impulze cevi v sistem Montaža ventila v povratek Montaža ventila v dovod Priključitev na cev Močno priporočamo da impulzno cev priključite na cevovod horizontalno ali navzgor To onemogoča nabiranje nečistoč v impulzni cevi in posledično slabo delovanje regulatorja Priključitev navzdol ni priporočljiva Montaža impulzne cevi 1 Odrežite cev pravok...

Page 10: ...mpulsního potrubí Jaké impulsní potrubí použít Použijte sadu impulsního potrubí AV nebo použijte následující potrubí Měď Ø 6 1 mm EN 12449 Připojení impulsního potrubí do systému Montáž na vratnou větev Montáž na přívodní větev Připojení na potrubí Impulsní potrubí doporučujeme nainstalovat na potrubí ve vodorovné poloze a směrem nahoru Tímto způsobem montáže zabráníte hromadění nečistot v impulsn...

Page 11: ...ładzie Montaż na rurociągu powrotnym Montaż na rurociągu zasilającym Podłączenie do rurociągu Zaleca się podłączenie rurki impulsowej do rurociągu albo poziomo albo od góry Podłączenie takie zapobiega gromadzeniu się zanieczyszczeń w rurce impulsowej co może spowodować wadliwe działanie regulatora Podłączenie rurki impulsowej od dołu rurociągu nie jest zalecane Montaż rurki impulsowej 1 Obciąć rur...

Page 12: ...мпульсной трубки Какие импульсные трубки использовать Используйте комплекты импульсных трубок типа AV или простую медную трубку Ø 6 1 мм по EN 12449 Подсоединение импульсной трубки к системе При установке регулятора на обратном трубопроводе При установке регулятора на подающем трубопроводе Подсоединение к трубопроводу Присоединять импульсную трубку к трубопроводу следует сбоку или сверху Это предо...

Page 13: ...amzdį Varinį Ø 6 1 mm EN 12449 Impulsinio vamzdelio prijungimas prie sistemos Montavimas grąžinimo vamzdyne Montavimas tiekimo vamzdyne Montavimas vamzdyne Labai rekomenduojame prijungti impulsinį vamzdelį prie vamzdyno šono arba viršaus Tai apsaugo nuo purvo kaupimosi impulsiniame vamzdelyje ir nuo galimų reguliatoriaus gedimų Prijungimas vamzdžio apačioje nerekomenduojamas Impulsinio vamzdelio m...

Page 14: ...k de volgende leiding Koper Ø 6 1 mm EN 12449 Aansluiting van impulsleiding in het systeem Montage in retour Montage in aanvoer Aansluiting op de leiding Installeer de impulsleiding verticaal omhoog of horizontaal op de leiding Dit voorkomt vervuiling van de impulsleiding en mogelijk slecht functioneren van de regelaar Aansluiting omlaag is niet aan te bevelen Impulsleiding montage 1 Snij de pijp ...

Page 15: ...dszerhez Szelep a visszatérő ágban Szelep az előremenő ágban Impulzusvezeték bekötése a csővezetékbe Az impulzusvezetéket erősen ajánlott vízszintesen vagy függőlegesen felfelé bekötni Ezzel elkerülhető a szennyeződés lerakódása az impulzusvezetékben és így a szabályozó rendellenes működése Az impulzusvezetéket nem ajánlott lefelé bekötni Az impulzusvezeték szerelése 1 Vágja el a csővezetéket a te...

Page 16: ...te Este recomandabil să instalaţi tubul de impuls pe conductă orizontal sau orientat în sus Astfel preveniţi acumularea de impurităţi în tubul de impuls şi posibile defecţiuni ale regulatorului Racordarea tubului orientat în jos nu este recomandată Montarea tubului de impuls 1 Tăiaţi conducta perpendicular pe axa sa şi neteziţi marginile 2 Apăsaţi tubul de impuls în racordul filetat până la capătu...

Page 17: ...73695010 DH SMT SI VI DB N3 8I Danfoss 04 2009 17 ...

Page 18: ...73695010 DH SMT SI VI DB N3 8I Danfoss 04 2009 18 ...

Page 19: ...73695010 DH SMT SI VI DB N3 8I Danfoss 04 2009 19 ...

Page 20: ...re is feltéve hogy e változtatások végrehajthatók a már elfogadott specifikáció lényeges módosítása nélkül Az ebben az anyagban található védjegyek az érintett vállalatok tulajdonát képezik A Danfoss és a Danfoss logo a Danfoss A S védjegyei Minden jog fenntartva Danfoss Kft H 1139 Budapest Váci út 91 Telefon 1 450 2531 Telefax 1 450 2539 E mail danfoss hu danfoss com www danfoss hu 73695010 DH SM...

Reviews: