background image

Instruction 

APP pump instruction APP 0.6-1.0, APP 1.5-2.5 and APP 3.0-3.5

3

180R9065  /  521B0733 /  DKCFN.PI.013.C4.2T  /  09.2012

The design of the system must ensure that self 

emptying of the pump during standstill is 

avoided.

The inlet pressure of the pump must never 

exceed the outlet pressure. This may typically 

occur in boosted or open-ended systems with 

direct water supply.

In order to avoid this it is recommended to install 

a pre-stressed check valve or a pressure switch in 

the pump inlet.

The opening pressure of the check valve must be 

bigger or equal to the inlet pressure.

2.1   Open-ended systems with water supply 

from a tank

(The numbers 1-3 refer to the drawing below.)

In order to eliminate the risk of cavitation, 

observe the following guidelines:

1) 

 Place the tank above the pump (water level 

in the tank should always be above the 

pump).

2) 

Place the inlet filter before the tank.

3) 

 Dimension the inlet line to obtain mini- 

mum pressure loss (large flow area, 

minimum pipe length, minimum number 

of bends/connections, fittings with small 

pressure losses).

1. Identification

2. 

System design

2.2   Open-ended systems with direct water 

supply

The pump is supplied with water direct from a 

booster pump.

The water pressure must not exceed 5 bar abs. 

(72.5 psi).

2.3  Problems with reversing pumps

If exposed to high pressure in the outlet while 

the electric motor is not energized, the pumps 

will start spinning backwards. This will not harm 

the pumps as long as the pressure in the inlet 

does not exceed the max. pressure of 5 bar.

If a non-return valve is mounted in the inlet line, 

a low-pressure relief valve will also be required. 

Alternatively a high-pressure check valve could 

be mounted in the pump discharge line to 

prevent the pump from reversing.

The dotted setup ensures that the inlet pressure 

does not exceed the 5 bar abs., when a non- 

return valve is mounted in the inlet.

6 bar

[87 psi]

Summary of Contents for APP 0.6

Page 1: ...APP 0 6 1 0 APP 1 5 2 5 and APP 3 0 3 5 MAKING MODERN LIVING POSSIBLE Lenntech info lenntech com Tel 31 152 610 900 www lenntech com Fax 31 152 616 289 info lenntech com Tel 31 152 610 900 www lenntec...

Page 2: ...ines for calculation of pressure losses 4 2 5 General comments on 4 3 Building up the pump unit 5 3 1 Mounting 5 3 2 Direction of rotation 5 3 3 Orientation 6 3 4 Protection from too high pressures 6...

Page 3: ...mp 2 Place the inlet filter before the tank 3 Dimension the inlet line to obtain mini mum pressure loss large flow area minimum pipe length minimum number of bends connections fittings with small pres...

Page 4: ...ng to below guidelines 2 5 General comments on Filtration A good ltration is vital to ensure a long and trouble free life of the pump When selecting a filter or strainer please note that filter materi...

Page 5: ...all to separate the inlet from the outlet end of the tank Monitoring It is recommended to continuously monitor the following conditions Water level in the tank Filter contamination Pressure inlet and...

Page 6: ...close to the pump as possible The opening characteristics of the valve must not result in peak pressures higher than 200 bar 2900 psi The valve outlet must not be connected directly to the pump suctio...

Page 7: ...ssure gauge on the high pressure side 5 3 Dry running When running the pump must always be connected to the water supply in order to avoid damage if it should run dry In systems with water tank it is...

Page 8: ...elf and there is thus no oil in the pump The pump requires no periodic replacements of seals and valve parts 6 2 Repair In case of irregular function in the pump please contact the Danfoss Sales Organ...

Reviews: