AKD 5000
Technical
data
Externals:
Enclosure ............................................................................................................................................. IP 20, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ................................................................................ 93 % (IEC 68-2-3) for storage/transport
Max. relative humidity ............................................... 95 % non condensing (IEC 721-3-3; class 3K3) for operation
Aggresive environment (IEC 721 - 3 - 3) .................................................................................. Uncoated class 3C2
Aggresive environment (IEC 721 - 3 - 3) ...................................................................................... Coated class 3C3
Ambient temperature IP 20 (high overload torque 160%) .......................
Max. 45°C (24-hour average max. 40°C)
Ambient temperature IP 20 (normal overload torque 110%) .................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 54 (high overload torque 160%) .......................
Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 54 (normal overload torque 110%) .................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 20/54 AKD 5011 500 V ....................................
Max. 40°C (24-hour average max. 35°C)
Derating for high ambient temperature, see the Design Guide
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance .....................................................................................
-10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
Derating for high air altitude, see the Design Guide
EMC standards applied, Emission .............................................................. EN 50081-1/2, EN 61800-3, EN 55011
EMC standards applied, Immunity .......................... EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, VDE 0160/1990.12
See section on special conditions in the Design Guide.
AKD 5000 Series protection:
•
Electronic motor thermal protection against overload.
•
Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature
reaches 90°C for IP 20. For IP 54, the cut-out temperature is 80°C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60°C.
•
The frequency converter is protected against short-circuiting on motor terminals U, V, W.
•
The frequency converter is protected against earth fault on motor terminals U, V, W.
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if
the intermediate circuit voltage gets too high or too low.
•
If a motor phase is missing, the frequency converter cuts out.
•
If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
•
If a mains phase is missing, the frequency converter will cut out when a load is placed on the motor.
MG.50.R3.02 -
15