Daily operation

With the AK-SM 800AL setup and receiving alarms, the following 
section describes typical daily use.

Acknowledging current alarms

When a new alarm or alarms are received by the AK-SM 800AL the 
alarm icon will update with the count of active and acknowledged 
alarms.  If configured to do so, the AK-SM 800AL will turn the front 
LED red and will emit an alarm buzzer sound.  The local relay on 
the AK-SM 800AL will also trigger (if configured to do so).

Note:

You do not have to be authorized to visualize alarm(s) in the 
AK-SM 800AL.  The user can view all current / Acknowledged 
and Cleared alarms, however to acknowledge and manage the 
alarm(s), user authorization is required.

To Acknowledge the alarm or alarms you must be authorized by 
entering user name and password (usually defined in step two of 
initial wizard setup, else configurable via Settings screen).  Once 
authorized, press the main alarm icon, new alarms text or the 
alarms menu icon – all three navigation paths will result in the 
‘Current Alarms’ screen being displayed.

Simplified alarm details will be shown on this screen, showing 
which system unit the alarm originated from and a description of 
the alarm.  For more details of the alarm, press the ‘info’ icon (or 
any location on the alarm line).  The alarm can be Acknowledged 
at this screen via the Acknowledge button.  The result of 
acknowledging the alarm is that all alerts (LED, buzzer, local alarm 
relay) will be de-activated.  The action of acknowledging an alarm 
or alarms will be captured in the audit trail and will also be shown 
in the current alarms screen as ‘Ack’.

Note:

By factory default the option to ‘bulk’ Acknowledge action via 
the use of the master check box is disabled, resulting in the need 
to individually acknowledge each active alarm.  By default, the 
alarm category filters are all ‘on’.  Based on customer or application 
preferences these filters can be used to only show relevant alarms 
from these groups. 

Note:

It is not possible to manually clear alarms, the cleared alarm state 
will be automatically set upon alarm error condition clearing.

Summary of Contents for AK-SM 800AL

Page 1: ...Alarm Logger AK SM 800AL User Guide ADAP KOOL Refrigeration Control System...

Page 2: ...of the System Manager host network utilizing IP Ethernet communications between all units Alarms raised at any System Manager 800 can be forward ed routed to the alarm logger for action and escalation...

Page 3: ...network Failures in host network will result in red indicator and visible screen saver icon Screen saver is activated after 5 minutes of no user input or im mediately after logging out The screen sav...

Page 4: ...can be assigned in the system The first user is by factory default the Supervisor level this user has access to all configuration screens in the system As part of the AK SM 800 AL setup process the co...

Page 5: ...ically set all detected host AK SM 800 units for alarm logger alarm action rout ing Manual adjustment of these alarm actions is possible per site specifications AK SM 800 host units For the AK SM 800A...

Page 6: ...f enabled Enable alarm logger reminder alerts Enabled Disabled A reminder alert will be triggered if there are any new or acknowledged alarms in the AK SM 800AL The time between alerts is configurable...

Page 7: ...in alarm icon new alarms text or the alarms menu icon all three navigation paths will result in the Current Alarms screen being displayed Simplified alarm details will be shown on this screen showing...

Page 8: ...the appropriate software to load During the software update a progress bar will be shown and typically the AK SM 800AL will reset Note Software must be located on the root directory of the USB Flash...

Page 9: ...a c 50 60 Hz Built in alarm relay Contact voltage Up to 240V Load AC 1 Ohmic Current rating 5 Amp AC 15 inductive Current rating 3 Amp LCD Active TFT colours thin film transistor SVGA 800 x 600 Size U...

Page 10: ...e right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications...

Reviews: