9. Navigate back to the Configuration -> Control -> Leak -> Alarms 

tab to enable alarms for each zone sensor if desired.

10. Navigate to the Configuration -> Control -> Refrigeration -> 

Circuits -> Setup tab. Choose the leak detector you wish to 
associate from the “Monitor leak detector” box. Choose the 
desired zone. Enable “Generate horn relay” and “Generate 
strobe relay” to “Yes” as desired. PPM triggers are configured 
here as well.

11. Navigate to the Configuration -> Control -> Refrigeration -> 

Addresses tab and go to the relay subtab to address the horn 
and strobe as desired.