Service Guide 

|

 AK-SM 800: Setup for HGM Leak Detector with Alarm and Strobe

AX279127907281en-000101 | 3

© Danfoss | ADAP-KOOL® | 2018.08  

5. Navigate to the Setup Tab

6. From the dropdown box, select the Leak Detector you wish to 

setup. Choose the Refrigerant, Full scale value, and enable each 
zone sensor that will be used.

7. Navigate to the addresses tab.

8. Go to the Sensors tab and address as desired.